Figure; Draft Regulator 7 Figure - CAC / BDP CBMAAA Installation Instructions Manual

Multipoise oil furnace input capacities 70,000-154,000
Table of Contents

Advertisement

Available languages

Available languages

Thisfurnace is certified for use witha Type"L" vent
(maximum f luegastemperature 30213 (5751=)). Thef Iue
pipe clearance knockout inthefront t oporsidepanel should
beremoved. Install theflueelbow sothatitexits thefurnace
cabinet through t hat o pening.
Pre-installation
vent system inspection
Before this furnace is installed,
it is strongly recommended
that any existing vent system be completely inspected.
On any chimney or vent, this should include the following:
a.
Inspection for any deterioration
in the chimney or vent.
If deterioration
is discovered,
the chimney
must
be
repaired or the vent replaced;
b.
Inspection to ascertain that the vent system is clear and
free of obstructions.
Any blockages
must be removed
before installing this furnace;
c.
Cleaning
the chimney
or vent if previously
used for
venting a solid fuel burning appliance or fireplace;
d.
Confirming that all unused chimney or vent connections
are properly sealed;
e.
Verification
that the chimney is properly lined and sized
per the applicable
codes. (Please refer to list of codes
in Part 1.2)
Masonry Chimneys
This furnace
may
be vented
into an existing
masonry
chimney.
However,
it must not be vented into a chimney
servicing a solid fuel-burning
appliance.
Before venting this
furnace into a chimney, the chimney must be checked for
deterioration
and repaired
if necessary. The chimney must
be properly lined and sized per local and/or national codes.
The chimney must be of sufficient area to accommodate
the
total flue products of all appliances vented into the chimney.
The following requirements
are provided for a safe venting
system:
a.
Ensure
that the chimney flue is clear of any dirt or
debris;
b.
Ensure
that the chimney
is not servicing
an open
fireplace;
c.
Never reduce the pipe size below the outlet size of the
furnace;
d.
All pipes should be supported, using the proper clamps
and/or straps. These supports
should
be installed
at
least every 4 feet;
e.
All horizontal runs of pipe should have at least 20 mm
of upward slope per 1 m (1/4" per 1');
f.
All runs of pipe should be as short as possible with as
few turns as possible;
g.
Seams should be tightly joined and checked for leaks;
h.
The flue pipe must not extend into the chimney but be
flush with the inside wail;
i.
The chimney must extend 0.9 m (3') above the highest
point where it passes through a roof of a building and at
least 0.6 m (2') higher than any portion of a building
within a horizontal distance of 3 m (10'). It shall also be
extended
at least
1.5
m (5')
above
the
highest
connected equipment flue collar;
j.
Check local codes for any variances.
Factory Built Chimneys
Approved
factory
built chimneys
may be used.
Refer to
chimney manufacturer's
instructions for proper installation.
2.4.4
Draft Regulator
The draft regulator supplied with the furnace must be used
for proper functioning.
Installation instructions are included
with the control.
2.4.5
Blocked vent shut-off (BVSO)
For chimney venting
All oil furnaces
installed
in Canada
must have a blocked
vent shut-off.
It is imperative
that this
device
be
installed
by a
qualified agency.
This device is designed to detect the insufficient evacuation
of combustion gases in the event of a vent blockage. In such
a case the thermal switch will shut down the oil burner. The
device will then need to be re-armed MANUALLY.
Please refer to Figures 2 to 8, the wiring diagrams,
Figures
12 and 13, and the detailed
instructions
supplied with the
BVSO for the installation and wiring procedures. The length
of wires supplied with the unit is such that the safety device
must be installed between the flue outlet of the appliance
and the draft regulator, as indicated in the instructions.
For more details, refer to the instructions
supplied with the
device itself, as well as section 3 of this manual.
FIRE, CARBON MONOXIDE POISONINC HAZARD
Failure to follow
this warning could result in personal
injury, death, and/or property damage.
DO NOT reset the device or restart the furnace unless
the cause of the interruption
has been identified and
corrected by a qualified agency. Ensure that the blocked
vent shut-off has been cleaned by a qualified agency
before placing into service. Annual inspection
and
cleaning of the blocked vent shut-off by a qualified
agency is required.
FIRE, CARBON MONOXIDE POISONINC HAZARD
Failure to follow
this warning could result in personal
injury, death, and/or property damage.
The
blocked
vent
shut-off
MUST
be inspected
and
maintained annually by a qualified agency.
It is also essential
that the BVSO be maintained
annually.
For more details
please refer to the instructions
supplied
with the device itself, as well as Section 4 of this Manual.