Combustion Check; Limit Control Check; Year Round Air Conditioning; Table 4 - CAC / BDP CBMAAA Installation Instructions Manual

Multipoise oil furnace input capacities 70,000-154,000
Table of Contents

Advertisement

Available languages

Available languages

3.4
COMBUSTION
CHECK
IMPORTANT:
The heat exchanger
metal surfaces
may
have oil and the baffle
insulation
also contains
binders.
These
products
will
burn
or evaporate
when
the unit
operates
for the first time.
Because
of this, the smoke
reading may be inexact during the first minutes of operation.
Therefore, the unit must operate during at least 60 minutes
before taking any readings to adjust the combustion quality.
Let the unit cool down before making any adjustments.
IMPORTANT:
The combustion check verification
MUST be I
performed
after
the
nozzle
replacement
or the
burner I
cleaning.
After
these
manipulations,
the
combustion I
parameters
are necessarily
modified.
Refer
also to the I
burner instruction manual.
I
In order to obtain optimum performance
from the oil burner,
the
following
set-up
procedures
must
be followed
by
referring
to the Technical
Specifications,
Table 5 in this
manual:
1.
A test kit to measure the smoke, flue draft and over-fire
pressure should be used in order to obtain the proper
air
band
setting.
Although
all
of
the
above
measurements
are required
for optimum
set up and
efficiency,
the most
important
reading that
must be
taken is the smoke number in the flue pipe, downstream
from the regulator;
2.
The proper smoke
number, as established
by way of
engineering
tests, is between 0 and 1. This degree of
smoke emission is commonly referred to as a "trace". It
is recommended
that a Bacharach
True Spot Smoke
Test kit or equivalent be used;
3.
Follow
the next steps
to do the combustion
check
verification:
a.
Drill a minimum proper diameter (about 9/32") test
hole in the flue pipe, approximately
18 inches from
the furnace breech;
b.
From a cold start, let the unit operate for about 5
minutes;
c.
Set the burner air setting until you have between 0
and 1 on the Bacharach Scale (or a "trace");
d.
Take a CO2 sample at the same test location where
the smoke reading was taken and make note of it;
e.
Adjust the burner air setting to obtain a CO2 reading
1.5% lower (or a 02 reading 2.0% higher) than the
reading associated with the "trace" of smoke;
f.
This method of adjusting
the burner will result in
clean
combustion
(Bacharach
smoke
scale
between
0 and a trace) and ensure
the proper
functioning of the system.
4.
A barometric draft regulator, supplied with the furnace,
must
be installed,
in order
to ensure
proper
draft
through the furnace. The barometric
damper must be
mounted with the hinge pins in a horizontal position and
the face of the damper vertical for proper functioning,
(see
instructions
included
with
damper).
After
the
furnace has been firing for at least five minutes, the
draft regulator
should be set to between -0.025" W.C.
and -0.035" W.C.;
5.
The
over
fire
pressure
that
is taken
through
the
observation door located in the centre of the front panel
above the burner is a measurement that is necessary to
determine
if there is a blockage in the heat exchanger
or
the
flue
pipe.
Please
refer
to the
Technical
Specifications
in this manual
for over
fire pressure
12
6.
3.5
values. A high pressure
condition
may be caused by
excessive combustion air due to the air band being too
wide open or a lack of flue draft (chimney
effect) or
some other blockage,
such as soot in the secondary
section of the heat exchanger or the use of an oversize
nozzle input or high pressure pump;
After all the set up procedures
mentioned
above have
been completed,
the burner should
be fired
and an
inspection
mirror should be used to observe the flame
pattern at the tip of the nozzle. Any irregularities
such
as burning
to one side or pulsating
flame
patterns
should be corrected by changing the nozzle.
LIMIT CONTROL CHECK
After the furnace
has been in operation
for at least 15
minutes, restrict the return air supply by blocking the filters
or closing the return registers and allow the furnace to shut
down on High Limit. The burner will shut OFF but the main
blower should continue to run.
Remove the restriction and the burner should come back on
in a few minutes.
3.6
YEAR ROUND AIR CONDITIONING
The furnace is designed for use in conjunction with cooling
equipment,
to provide
year round
air conditioning.
The
blower
has
been
sized
for
both
heating
and
cooling;
however, the fan motor speed may need to be changed to
obtain the necessary cooling airflow.
3.7
HEATING
The blower
speed
is factory
set to deliver
the required
airflow at normal duct static pressure.
3.8
COOLING
The blower speed may be adjusted in the field to deliver the
required
airflow
for cooling
applications,
as outlined
in
Table 4.
3.9
CONSTANT BLOWER SWITCH
This furnace is equipped with a constant low speed blower
option.
Whenever
the room thermostat
is not calling for
heating or cooling, the blower will run on low speed in order
to provide air circulation. If this constant blower option is not
desired, the rocker switch on the side of the control box can
be used to turn it off.
4.0
MAINTENANCE
I
Before performing
any service functions,
make sure that I
all
utilities
are
turned
"OFF"
upstream
from
the I
appliance,
unless
operations
specifically
require
the I
power to be on. Failure to comply with this warning will I
cause a fire hazard and/or bodily harm.
I

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cmbaar

Table of Contents