Figure 9; Operation; Supply Air Adjustments; Operational Checklist - CAC / BDP CBMAAA Installation Instructions Manual

Multipoise oil furnace input capacities 70,000-154,000
Table of Contents

Advertisement

Available languages

Available languages

3.0
OPERATION
3.1
SUPPLY AIR ADJUSTMENTS
This unit is equipped
with 4-speed
blower
motors. The
supply
air
must
be
adjusted
based
on
heating/air
conditioning
output
and
the static
pressure
of the duct
system. For the desired air flow please refer to Table 3 and
4 as well as the air flow Table 6 based on static pressure in
the Technical Specifications,
Table 5, of this manual.
Table 3 : Blower speed adjustments,
4 speed motor,
FURNACE
MODEL
CBM SIZE 105
CBM SIZE 120
heating
mode
HEATING
INPUT
0.50 USGPH
0.65 USGPH
0.75 USGPH
0.85 USGPH
1.00 USGPH
1.10 USGPH
RECOMMENDED
BLOWER SPEED
MED-LOW
MED-HIGH
HIGH
MED-LOW
MED-HIGH
HIGH
To effect the adjustment,
the RED and BLUE wires can be
changed on the motor. Also, please refer to the position of
the wires on the electronic board of the unit and consult the
wiring diagrams.
If the heating
and the air conditioning
speeds are the same, the RED wire must be moved to
"UNUSED LEADS" on the electronic
board and the jumper
provided with the BLUE wire must be used between the
"HEAT" and "COOL" terminals.
Table
4 : Blower speed adjustments,
4 speed motor,
FURNACE
MODEL
CBM SIZE 105
CBM SIZE 120
cooling
mode
COOLING
CAPACITY
2.0 TONS
2.5 TONS
3.0 TONS
3.5 TONS
4.0 TONS
5.0 TONS
RECOMMENDED
BLOWER SPEED
MED-LOW
MED-HIGH
HIGH
MED-LOW
MED-HIGH
HIGH
The blower start/stop delays can be adjusted by positioning
the DIP switches on the electronic
board as shown on the
Figure 9.
Fi.qure 9 : Blower Start/Stop
delays Board # 1158
oi
2i;4
iqF=Pq
i
i20
Sec
;
6 'vin
DELAY ON
DELAY OFF
,Jl
2i
_
,J
i
9,{ Sec
J
4 I',,'lin
DELAY ON I C'EL£Y 'OFF
i
0
N
l
60 Sec
{DELAY ON
2J.34
3E t
i
2 v it'
DELAY OFF
s, 12:_4
,t ,',tl=Et
i
........
_
I
v ir
DEL_,Y
ON
i {},ELAY
OFF
3,2
OPERATIONAL
CHECKLIST
Before
starting
up the unit, be sure
to check
that the
following items are in compliance:
1.
The electrical
installation,
the oil supply
system,
the
venting system, combustion air supply and ventilation;
2.
The blower access door is in place and the blower rail
locking screws are well tightened;
3.
The
Blocked
Vent
Shut-Off
(BVSO)
is
installed
according to instructions (for chimney venting);
4.
The oil supply valve is open;
5.
The flame
observation
door and
the two
clean-out
access doors (located at the front of the unit) or well
closed;
6.
The burner "Reset"
button
is well pushed
in or re-
armed;
7.
The preliminary
air adjustments
on the burner comply
with the technical specifications
in this manual;
8.
The blower
speed
adjustments
for
heating
and
air
conditioning
are
appropriate
and
according
to the
specifications
in this manual;
9.
The blower start/stop delays are satisfactory;
10. The thermostat of the room is in the heating mode and
is set higher than the ambient temperature.
To start the unit, turn the main electrical switch on.
Do not tamper
with the unit or its controls.
Call
a
qualified service technician.
3.3
1.
2.
PURGING THE OIL LINE
A 10-micron
(or less) oil filter should
be installed
as
closely to the burner as possible with all oil burners, but
it is essential
for burners with a low firing rate. We
recommend
the use of a low pressure drop oil filter with
a capacity greater than that of the fuel pump;
On a new installation,
the air trapped
in the oil line
leading from the tank to the nozzle must be thoroughly
purged in order to prevent excessive after drip. The oil
pump is equipped with a special fitting that facilitates
the purging of any air between
it and the tank. The
proper procedure
for performing
this operation
is as
follows:
a.
Place a piece of 1/4" diameter clear plastic tubing
over the purge fitting on the oil pump;
b.
Start the oil burner, then open the purge fitting and
allow the burner to run until the purge tube
is
completely free of air bubbles;
c.
At this point tighten
the purge fitting,
which will
allow the oil to run to the nozzle and fire the burner.
If the purging takes longer than 15 seconds and no
flame
has been established
the burner will stop.
Push the reset button on top of the Primary Control
to restart the burner.
For detailed information
on the operation of the Primary
Control please refer to the instructions included with the
furnace or the burner.
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cmbaar

Table of Contents