RS485 Communications Circuit
•
Power limited
•
Supervised
•
Voltage: 24 VDC nominal
•
Current:
0.5 amp maximum available for auxiliary power outputs, RS485 circuit and option boards
0.4 amp maximum for RS485 circuit
•
Maximum wire loop resistance: 25 ohms/line
•
Communications: RS485
Addressable Device Circuit
•
Power limited
•
Supervised
•
Voltage: 24 VDC nominal
•
Maximum Current (shorted): 0.25A
•
Maximum wire loop resistance: 20 ohms/line
•
One Style 4 or 6 circuit
•
60 detectors and modules max.
•
1 accessory output per device
Municipal Tie (Optional Municipal Tie Board Model FS-MT)
CA
Reverse Polarity: Selectable for Alarm with Trouble or Alarm only operation
•
Power limited
•
Supervised by receiver for short or open circuit.
•
Supervised by control unit for grounded circuit.
•
Voltage: 24 VDC nominal
•
Current: 0.020A maximum (normal or trouble)
•
Current: 0.025A maximum (shorted)
•
Ripple: 1.5 VAC maximum
CT
Reverse Polarity: Programmable for Trouble or Supervisory or either operation
•
Power limited
•
Supervised by receiver for short or open circuit.
•
Supervised by control unit for grounded circuit.
•
Voltage: 24 VDC nominal
•
Current: 0.020A maximum (normal or alarm)
•
Current: 0.025A maximum (shorted)
•
Ripple: 1.5 VAC maximum
LE
Local Energy
•
Not power limited
•
Supervised for open or grounded circuit by control unit.
•
Voltage: 24 VDC nominal
•
Standby Current: 0.007A maximum
•
Alarm Current: 0.400A maximum
•
Ripple: 1.5 VAC maximum
•
Maximum wire loop resistance: 30 ohms
•
Trip coil impedance: 14.5 ohms
RS232 Output (Optional RS232 Board Model FS-232)
•
Power limited
•
Not supervised
•
Voltage Range: -15 VDC to +15 VDC
•
Maximum Current (shorted): 0.050A
•
Baud Rate: 4800
•
Maximum wire loop resistance: 25 ohms
P/N 315-699461