WIRING SEPARATION

All high voltage and non-power l i mited wiring must be kept separate from power limited wiring. A ¼"
separation must be maintained, with high voltage and non-power limited wiring running in separate
conduit openings from power limited wiring.
A
B

PRIMARY AND SECONDARY POWER WIRING

The AC main connections and the battery connections must be made along the left-hand side of the
board. Route all high voltage and non-power limited wiring together and away from power limited wiring.
120VAC 60Hz
1.3A max., Supervised
Non-Power Limited
P/N 315-699461
Technical Manuals Online! - http://www.tech-man.com
C
E
1
3
2*
D
G
AC
N
GND
Keep All Non-Power Limited Wiring
Separate from Power Limited Wiring
A.
Non-power limited - High Voltage
F
(AC power) or B
B.
Non-power limited - High Voltage
(AC power) or A
C.
Power limited
D.
Non-power limited
(Battery If external enclosure required)
E.
Non-power limited
(Phone line or local energy box)
F.
Power limited or G
G.
Power limited or F
24V Battery Set
Non-Power Limited
26
(7 to 38AH)
Supervised

Hide quick links: