Style 6 provides redundant communication paths.
Note:
Addressable Devices:
Detectors, Monitor Modules, or Control Modules up to a maximum of 60 devices per addressable
device circuit. Maximum of 20 devices between Isolator Modules. Maximum of 12 Isolator
Modules per addressable device circuit.
P/N 315-699461
Technical Manuals Online! - http://www.tech-man.com
ADDRESSABLE DEVICE CIRCUIT
WIRING / OPERATION COMPARABLE TO NFPA STYLE "6"