Style 4 wiring permits branching of circuit connections. The control equipment supervises modules
because they are active and must respond periodically to the control unit's interrogation.
Note:
Addressable Devices:
Detectors, Monitor Modules, or Control Modules up to a maximum of 60 devices per addressable
device circuit. Maximum of 20 devices per Isolator Module. Maximum of 12 Isolator Modules per
addressable device circuit.
P/N 315-699461
Technical Manuals Online! - http://www.tech-man.com
ADDRESSABLE DEVICE CIRCUIT
WIRING / OPERATION COMPARABLE TO NFPA STYLE "4"
SUPERVISED,
POWER LIMITED
TO OPTIONAL
BRANCH(ES) OF
LOOP CIRCUIT