Peco Performance Pro T4000 serIes Installation Manual page 6

Hide thumbs Also See for Performance Pro T4000 serIes:
Table of Contents

Advertisement

Available languages

Available languages

taBle 2. aDvanceD conFIGUratIon: servIce menUs
To access Service Menus, simultaneously press lower left and lower right keys. Changed values are automatically retained. Service Menu availability is dependent upon system type and
upon system configuration. Note: The Remote Indoor Zone Sensor must be enabled in the Service Menus (see Service Menu 170).
menU
FeatUre
Schedule Format
100*
Daylight-Saving
101
Time
System Type
110
Fan Control
120
(heating)
Changeover valve
130
(B/O terminal)
Auxiliary Heat
140
Backlight
150
Remote Sensor
170
Furnace Filter
230
Change Reminder
Number of Program
240
Periods
Clock format
12 or 24 Hours
250
Temperature Format
260
(°F or °C)
Fan Off Delay Heat
270
Fan Off Delay Cool
280
Range Low
290
Range High
300
Setback Low
Off; 50-82°F or
310
Setback High
Off; 58-90°F or
320
Zone Temp Offset
330
© COPYRIGHT 2010 PECO, INC. ALL RIGHTS RESERVED.
PECO Wave PRO and PECO are registered trademarks of PECO, Inc. The PECO logo is a trademark of PECO, Inc.
oPtIons
stD.moDel
DeFaUlt
0-3
1
0,1
0
1-11
1
0,1
0
0,1
0
0,1
0
0,1
0
0-1
0
0; 30; 60; 90;
0
120; 365
2; 4 events
4
12
0,1
1
0-99 Seconds
0
0-99 Seconds
0
50-90 °F or
50°F (10°C)
10-32°C
50-90 °F or
90°F (32°C)
10-32°C
55°F (13°C)
11-27°C
90°F (32°C)
11-32°C
+/-9°F or +/-
0°F (18 °C)
4.5°C
DescrIPtIon / comments
Select the schedule format on the Performance PRO T4000 Series.
0 =
nonprogrammable
1 =
programmable
2 =
5-1-1 schedule
3 =
5-2 schedule
Select daylight-saving time as it follows standard format in U.S.: It begins second Sunday of March at
2:00 AM and ends on the first Sunday of November at 2:00 AM.
0 =
Disabled
1 =
Enabled (2007 US Format)
Select the appropriate system configuration (determines available Service Menus).
1 =
1 Heat/1 Cool conventional
2 =
1 Heat/1 Cool heat pump
3 =
Heat only without fan (2-wire systems)
4 =
Heat only with fan
5 =
Cool only
6 =
2 Heat/1 Cool heat pump (with auxiliary heat) and Emergency (Em) heat
7 =
2 Heat/2 Cool multistage conventional
8 =
2 Heat/ 1 Cool multistage conventional
9 =
1 Heat/ 2 Cool multistage conventional
10 = 2 Heat/ 2 Cool heat pump (no aux. heat)
11= 3 Heat/ 2 Cool heat pump (with auxiliary heat) and Emergency (Em) heat
0 = Fossil Fuel: Gas/Oil/Propane heat (equipment controls heating fan)
1 = Electric Furnace (thermostat controls heating fan)
0 =
B/O terminal controls valve in cooling
1 =
B/O terminal controls valve in heating
0 = Electric backup heat
1 =
Fossil fuel backup heat
0 =
Backlight temporarily on
1 =
Backlight always on (low intensity, 24V only)
Select sensor if used (connected to the S1 Terminal). Contact PECO for more information on the Indoor
Remote Zone Sensor.
0 =
No Sensor
1 =
Indoor Sensor
Set a filter reminder timer; appears on digital display when timer expires (if programmed).
0 = Off
10 days; 30 days; 60 days; 90 days; 120 days; 365 days
2 =
2 events per day
4 =
4 events per day
12 = 12-hour clock mode
24 = 24-hour clock mode
0 =
Celsius
1 =
Fahrenheit
Select the amount of time (in seconds) that the fan will run after the thermostat heat outputs are turned
off.
Select the amount of time (in seconds) that the fan will run after the thermostat cool outputs are turned
off.
Choose the lowest selectable temperature setpoint value.
Choose the highest selectable temperature setpoint value.
Select the heat setpoint for setback mode.
0 =
Off
50-82°F (11-27°C)
Select the cool setpoint for setback mode.
0 =
Off
58-90°F (11-32°C)
Adjusts the displayed value; may differ from actual zone temperature.
6
P/N 70476 3220-2265 REV 01