1. SPECIFICATIONS R2-Series I.R2-Series 1. SPECIFICATIONS Model PURY-P200YNW-A2/TR2 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 22.4 BTU/h 76,400 Power input 6.54 Current input 11.0-10.4-10.1 kW/kW 3.42 Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) cooling *3 Outdoor D.B.
Page 5
1. SPECIFICATIONS R2-Series Model PURY-P250YNW-A2/TR2 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 28.0 BTU/h 95,500 Power input 9.92 Current input 16.7-15.9-15.3 kW/kW 2.82 Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F) Heating capacity *2 kW...
Page 6
1. SPECIFICATIONS R2-Series Model PURY-P300YNW-A2/TR2 (-BS) Number of HBC Single HBC Double HBC Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 33.5 BTU/h 114,300 Power input 13.13 11.12 Current input 22.1-21.0-20.2 18.7-17.8-17.1 kW/kW 2.55 3.01 Temp. range of Indoor W.B.
Page 7
1. SPECIFICATIONS R2-Series Model PURY-P350YNW-A2/TR2 (-BS) Number of HBC Single HBC Double HBC Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 40.0 BTU/h 136,500 Power input 16.26 13.24 Current input 27.4-26.0-25.1 22.3-21.2-20.4 kW/kW 2.46 3.02 Temp. range of Indoor W.B.
Page 8
1. SPECIFICATIONS R2-Series Model PURY-P400YNW-A2/TR2 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 45.0 BTU/h 153,500 Power input 16.65 Current input 28.1-26.7-25.7 kW/kW 2.70 Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F) Heating capacity *2 kW...
Page 9
1. SPECIFICATIONS R2-Series Model PURY-P450YNW-A2/TR2 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 50.0 BTU/h 170,600 Power input 17.92 Current input 30.2-28.7-27.7 kW/kW 2.79 Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F) Heating capacity *2 kW...
Page 10
1. SPECIFICATIONS R2-Series Model PURY-P500YNW-A2/TR2 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 56.0 BTU/h 191,100 Power input 24.03 Current input 40.5-38.5-37.1 kW/kW 2.33 Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F) Heating capacity *2 kW...
Page 11
1. SPECIFICATIONS R2-Series Model PURY-EP200YNW-A2/TR2 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 22.4 BTU/h 76,400 Power input 5.84 Current input 9.8-9.3-9.0 kW/kW 3.83 Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F) Heating capacity *2 kW...
Page 12
1. SPECIFICATIONS R2-Series Model PURY-EP250YNW-A2/TR2 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 28.0 BTU/h 95,500 Power input 8.77 Current input 14.8-14.0-13.5 kW/kW 3.19 Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F) Heating capacity *2 kW...
Page 13
1. SPECIFICATIONS R2-Series Model PURY-EP300YNW-A2/TR2 (-BS) Number of HBC Single HBC Double HBC Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 33.5 BTU/h 114,300 Power input 12.05 10.24 Current input 20.3-19.3-18.6 17.2-16.4-15.8 kW/kW 2.78 3.27 Temp. range of Indoor W.B.
Page 14
1. SPECIFICATIONS R2-Series Model PURY-EP350YNW-A2/TR2 (-BS) Number of HBC Single HBC Double HBC Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 40.0 BTU/h 136,500 Power input 14.76 12.01 Current input 24.9-23.6-22.8 20.2-19.2-18.5 kW/kW 2.71 3.33 Temp. range of Indoor W.B.
Page 15
1. SPECIFICATIONS R2-Series Model PURY-EP400YNW-A2/TR2 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 45.0 BTU/h 153,500 Power input 14.28 Current input 24.1-22.9-22.0 kW/kW 3.15 Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F) Heating capacity *2 kW...
Page 16
1. SPECIFICATIONS R2-Series Model PURY-EP450YNW-A2/TR2 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 50.0 BTU/h 170,600 Power input 16.83 Current input 28.4-26.9-26.0 kW/kW 2.97 Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F) Heating capacity *2 kW...
Page 17
1. SPECIFICATIONS R2-Series Model PURY-EP500YNW-A2/TR2 (-BS) Power source 3-phase 4-wire 380-400-415 V 50/60 Hz Cooling capacity *1 kW 56.0 BTU/h 191,100 Power input 21.22 Current input 35.8-34.0-32.8 kW/kW 2.63 Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F) cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F) Heating capacity *2 kW...
2. OPERATION TEMPERATURE RANGE R2-Series 2. OPERATION TEMPERATURE RANGE Cooling only Range for continuous operation Continuous operation not recommended Outdoor temperature Heating only Continuous operation not recommended Range for continuous operation Continuous operation not recommended Outdoor temperature Combination of cooling/heating operation (Cooling main or Heating main) Indoor temperature Outdoor temperature Cooling...
3. CAPACITY TABLES R2-Series 3. CAPACITY TABLES Section 3-1. Shows an example of how to select the indoor and outdoor units according to the required heating/cooling load. Section 3-2. through 3-5. Show the actual correction data of indoor and outdoor units. MEES24K036...
3. CAPACITY TABLES R2-Series 3-1. Correction by temperature HYBRID CITY MULTI could have varied capacity at different designing temperature. Using the nominal cooling/heating capacity value and the ratio below, the capacity can be observed at various temperature. Indoor unit temperature correction PURY- P200YNW-A2/TR2 P250YNW-A2/TR2...
Page 21
3. CAPACITY TABLES R2-Series Indoor unit temperature correction PURY- P200YNW-A2/TR2 P250YNW-A2/TR2 To be used to correct indoor unit capacity only Nominal 25.0 31.5 Heating 85,300 107,500 BTU/h Capacity Input 6.49 10.06 PURY- EP200YNW-A2/TR2 EP250YNW-A2/TR2 Nominal 25.0 31.5 Heating 85,300 107,500 BTU/h Capacity Input...
Page 22
3. CAPACITY TABLES R2-Series Indoor unit temperature correction PURY- P300YNW-A2/TR2 P350YNW-A2/TR2 P400YNW-A2/TR2 To be used to correct indoor unit capacity only Nominal 33.5 40.0 45.0 Cooling 114,300 136,500 153,500 BTU/h Capacity Input 13.13 16.26 16.65 PURY- EP300YNW-A2/TR2 EP350YNW-A2/TR2 EP400YNW-A2/TR2 Nominal 33.5 40.0 45.0...
Page 23
3. CAPACITY TABLES R2-Series Indoor unit temperature correction PURY- P300YNW-A2/TR2 P350YNW-A2/TR2 P400YNW-A2/TR2 To be used to correct indoor unit capacity only Nominal 33.5 45.0 50.0 Heating 114,300 153,500 170,600 BTU/h Capacity Input 11.35 13.88 14.88 PURY- EP300YNW-A2/TR2 EP350YNW-A2/TR2 EP400YNW-A2/TR2 Nominal 37.5 45.0 50.0...
Page 24
3. CAPACITY TABLES R2-Series Indoor unit temperature correction PURY- P450YNW-A2/TR2 P500YNW-A2/TR2 To be used to correct indoor unit capacity only Nominal 50.0 56.0 Cooling 170,600 191,100 BTU/h Capacity Input 17.92 24.03 PURY- EP450YNW-A2/TR2 EP500YNW-A2/TR2 Nominal 50.0 56.0 Cooling 170,600 191,100 BTU/h Capacity Input...
Page 25
3. CAPACITY TABLES R2-Series Indoor unit temperature correction PURY- P450YNW-A2/TR2 P500YNW-A2/TR2 To be used to correct indoor unit capacity only Nominal 56.0 63.0 Heating 191,100 215,000 BTU/h Capacity Input 17.39 19.09 PURY- EP450YNW-A2/TR2 EP500YNW-A2/TR2 Nominal 56.0 63.0 Heating 191,100 215,000 Capacity BTU/h Input...
Page 26
3. CAPACITY TABLES R2-Series Correction by temperature (COP Priority Mode) HYBRID CITY MULTI could have various capacities at different designing temperatures. Using the nominal cooling/heating capacity values and the ratios below, the capacity can be found for various temperatures. To select COP priority mode, SW4 (935) must be set to ON. Indoor unit temperature correction PURY- P200YNW-A2/TR2...
Page 27
3. CAPACITY TABLES R2-Series COP Priority Mode Indoor unit temperature correction PURY- P200YNW-A2/TR2 P250YNW-A2/TR2 To be used to correct indoor unit capacity only Nominal 25.0 31.5 Heating 85,300 107,500 BTU/h Capacity Input 6.49 10.06 PURY- EP200YNW-A2/TR2 EP250YNW-A2/TR2 Nominal 25.0 31.5 Heating 85,300 107,500...
Page 28
3. CAPACITY TABLES R2-Series Indoor unit temperature correction PURY- P300YNW-A2/TR2 P350YNW-A2/TR2 P400YNW-A2/TR2 To be used to correct indoor unit capacity only Nominal 33.5 40.0 45.0 Cooling 114,300 136,500 153,500 BTU/h Capacity Input 13.13 16.26 16.65 PURY- EP300YNW-A2/TR2 EP350YNW-A2/TR2 EP400YNW-A2/TR2 Nominal 33.5 40.0 45.0...
Page 29
3. CAPACITY TABLES R2-Series COP Priority Mode Indoor unit temperature correction PURY- P300YNW-A2/TR2 P350YNW-A2/TR2 P400YNW-A2/TR2 To be used to correct indoor unit capacity only Nominal 33.5 45.0 50.0 Heating 114,300 153,500 170,600 BTU/h Capacity Input 11.35 13.88 14.88 PURY- EP300YNW-A2/TR2 EP350YNW-A2/TR2 EP400YNW-A2/TR2 Nominal...
Page 30
3. CAPACITY TABLES R2-Series Indoor unit temperature correction PURY- P450YNW-A2/TR2 P500YNW-A2/TR2 To be used to correct indoor unit capacity only Nominal 50.0 56.0 Cooling 170,600 191,100 BTU/h Capacity Input 17.92 24.03 PURY- EP450YNW-A2/TR2 EP500YNW-A2/TR2 Nominal 50.0 56.0 Cooling 170,600 191,100 BTU/h Capacity Input...
Page 31
3. CAPACITY TABLES R2-Series COP Priority Mode Indoor unit temperature correction PURY- P450YNW-A2/TR2 P500YNW-A2/TR2 To be used to correct indoor unit capacity only Nominal 56.0 63.0 Heating 191,100 215,000 BTU/h Capacity Input 17.39 19.09 PURY- EP450YNW-A2/TR2 EP500YNW-A2/TR2 Nominal 56.0 63.0 Heating 191,100 215,000...
3. CAPACITY TABLES R2-Series 3-2. Correction by total indoor HYBRID CITY MULTI system has different capacities and inputs when many combinations of indoor units with different total ca- pacities are connected. Using following tables, the maximum capacity can be found to ensure the system is installed with enough capacity for a particular application.
3. CAPACITY TABLES R2-Series 3-3. Correction by piping length A decrease in cooling/heating capacity will occur due to piping length increase. Using the following correction factors according to the equivalent length of the piping shown at 3-3-1 and 3-3-2 the capacity can be calculated. 3-3-3 shows how to obtain the equiv- alent length of piping.
Page 37
3. CAPACITY TABLES R2-Series PURY-(E)P400YNW-A2/TR2(-BS) PURY-(E)P400YNW-A2/TR2(-BS) Total capacity of indoor unit 0.99 0.95 0.98 0.90 0.97 0.85 0.96 0.80 0.95 0.94 0.75 0.93 0.70 0.92 0.65 0.91 HBC to outdoor unit refrigerant piping equivalent length (m) Water piping equivalent length to farthest indoor unit (m) PURY-(E)P450YNW-A2/TR2(-BS) PURY-(E)P450YNW-A2/TR2(-BS) Total capacity of indoor unit...
Page 38
3. CAPACITY TABLES R2-Series 3-3-2. Heating capacity correction PURY-(E)P200YNW-A2/TR2(-BS) PURY-(E)P200YNW-A2/TR2(-BS) 1.00 0.99 0.98 0.97 0.96 0.90 0.95 0.94 0.93 0.92 0.80 0.91 HBC to outdoor unit refrigerant piping equivalent length (m) Water piping equivalent length to farthest indoor unit (m) PURY-(E)P250, 300YNW-A2/TR2(-BS) PURY-(E)P250, 300YNW-A2/TR2(-BS) 1.00...
3. CAPACITY TABLES R2-Series 3-3-3. How to obtain the equivalent piping length Refrigerant pipe 1. PURY-(E)P200YNW(-BS) Equivalent length = (Actual piping length to the farthest indoor unit) + (0.35 × number of bends in the piping) [m] 2. PURY-(E)P250, 300YNW(-BS) Equivalent length = (Actual piping length to the farthest indoor unit) + (0.42 ×...
3. CAPACITY TABLES R2-Series 3-5. Correction by antifreeze solution concentration In HYBRID CITY MULTI system, antifreeze solution should be used to prevent the system from freezing. Refer to the following graphs for the capacity correction by antifreeze solution. Refer to 3-5-1 for antifreeze solution concentration, 3-5-2 and 3-5-3 for capacity correction by antifreeze solution concentration.
4. ELECTRICAL WORK R2-Series 4-1. Power supply for Outdoor unit 4. ELECTRICAL WORK 4-1-1. Electrical characteristics of the outdoor unit in cooling mode Symbols: MCA: Max Circuit Amps RLA: Rated Load Amps SC: Starting Current Power Units Compressor RLA(A)(50/60Hz) supply PURY-P-YNW-A2/TR2 Unit Combination Voltage...
5. M-NET CONTROL R2-Series 5-1. Address setting 5. M-NET CONTROL 5-1-1. Rule of setting address Unit Address setting Example Note Use the most recent address within the same group of indoor units. Indoor unit 01 ~ 50 The smallest address of indoor unit in same refrigerant system + 50 Assign sequential address numbers to the outdoor units in one refrigerant circuit system.
The maximum operation pressure of R410A air conditioner is 4.30 MPa [623psi]. The refrigerant piping should ensure the safety under the maximum operation pressure. MITSUBISHI ELECTRIC recommends pipe size as Table 1, or You shall follow the local industrial standard. Pipes of radical thickness 0.7mm or less shall not be used.
6. PIPING DESIGN R2-Series 6-2. Piping Design 6-2-1. Restrictions on pipe length CMB-WM108V-AA + CMB-WM108V-BB (CMB-WM1016V-AA) (CMB-WM1016V-BB) (~(E)P350) HBC (Main-HBC) HBC (Sub-HBC) Branch joint (field supply) (W/WP/WL10-W/WP/WL80) Max. 3 sets for 1 port. Total capacity < = W/WP/WL80 Junction pipe (field supply) OU: Outdoor unit, IU: Indoor unit (Unit: m) Increaser...
Page 45
6. PIPING DESIGN R2-Series 1. Refrigerant and water pipe size (1) Refrigerant pipe between outdoor unit and HBC controller (Part A, A1, A2, and A3) Use of one HBC controller HBC controller Unit model Model name High pressure side Low pressure side PURY-(E)P200 ø15.88 (Brazing) ø19.05 (Brazing)
Page 46
6. PIPING DESIGN R2-Series Pump 2 circuit Pump 1 circuit Pump 2 circuit Pump 1 circuit 10 11 13 14 15 16 Fig. B Pump 2 circuit Pump 1 circuit Fig. C Note: 1 To connect multiple indoor units to a port Maximum total capacity of connected indoor units: W/WP/WL80 Maximum number of connectable indoor units: 3 units Branch joints are field-supplied.
6. PIPING DESIGN R2-Series 6-2-2. Drain piping work 1. Drain piping work For Main-HBC and Sub-HBC controller Ensure that the drain piping is sloped downward (sloped gradient of more than 1/100) toward the discharge side. If it is impossible to take any downward pitch, use an optionally available drain pump to obtain a downward pitch of more than 1/100.
6. PIPING DESIGN R2-Series For Sub-HBC controller For Sub-HBC controller, connect the drain pipe by following the steps described below. 1. Insert the drain hose (accessory) into the drain port (insertion margin: 32 mm). (The drain hose must not be bent more than 45° to prevent the hose from breaking or clogging.) (Attach the hose with glue, and fix it with the band (small, accessory).) 2.
6. PIPING DESIGN R2-Series 6-2-3. Connecting water pipe work Please observe the following precautions during installation. 1. Important notes on water pipework installation The design pressure of the HBC controller water system is 0.6MPa. Use water pipe-work with a design pressure of at least 1.0MPa. When performing a water leak check, please do not allow the water pressure to go above 0.3MPa.
6. PIPING DESIGN R2-Series 2. Water pipe insulation 1. Connect the water pipes of each indoor unit to the same (correct) end connection numbers as indicated on the indoor unit connection section of each HBC controller. If connected to wrong end connection numbers, there will be no normal operation.
6. PIPING DESIGN R2-Series 5. Leakproof the water pipework, valves and drain pipework. Leakproof all the way to, and include pipe ends so that condensation cannot enter the insulated pipework. 6. Apply caulking around the ends of the insulation to prevent condensation getting between the pipework and insulation. 7.
Page 52
6. PIPING DESIGN R2-Series 6-3. Refrigerant charging calculation Indoor 1: 50 A: ø19.05 42 m Outdoor unit (~(E)P350) 2: 50 3: 50 4: 40 Outdoor P250 The total length of each liquid line is as follows: Indoor unit ø19.05: A = 42 m, = 3.0 Therefore, Additional refrigerant charge...
6. PIPING DESIGN R2-Series 6-4. Water piping 6-4-1. Precautions for water piping Consider the following when installing a water piping system. 1. Design pressure of the water piping Use a water pipe that is strong enough to withstand the design pressure (1.0 MPa). 2.
Page 54
6. PIPING DESIGN R2-Series 6-4-2. Notes on corrosion 1. Water quality It is important to check the water quality beforehand. See table below (Circulating water/Makeup Water Quality Standards). Lower mid-range Tendency temperature water system Recirculating Items water Make-up Scale- Corrosive [20<T<60°C] water forming...
6. PIPING DESIGN R2-Series 6-5. Compatibility <Horizontal type Main HBC connection> Outdoor/Heat source unit Main 1 Sub 1 Main 2 Sub 2 Compatibility WM-V-AA type – – – Compatible WP type – – – Compatible WM-V-AA type WM-V-BB type – –...
Page 56
6. PIPING DESIGN R2-Series <Vertical type Main HBC connection> Outdoor/Heat source unit Main 1 Sub 1 Sub 2 Sub 3 Compatibility WM-F-AA type – – – Not compatible WM-F-AA type WM-V-BB type – – Not compatible WM-F-AA type WM-V-AB type –...
CONTENTS Installation information Installation information I.Installation information 1. Installation information ..........................2 1-1. General precautions ........................2 1-2. Precautions for Indoor unit, Hydro unit, and HBC controller ............4 1-3. Precautions for outdoor unit/heat source unit .................. 5 1-4. Precautions for control-related items ....................6 MEES20K081...
1. Installation information Installation information I.Installation information 1. In stallation information * Refer to the enclosed Installation Manual for details on installation. Arrange to have an expert install the system correctly. 1-1. General precautions 1-1-1. Usage The air-conditioning system described in this DATA BOOK is designed for human comfort. This product is not designed to assist in the preservation of food, provide conditions to maintain plants or animals, or stabilize environments for the preservation of precision equipment or art objects.
Ensure that there is enough space around each unit. 1-1-7. Optional accessories Only use accessories recommended by Mitsubishi Electric. Consult your local distributor or a qualified technician when installing them. Improper installation by an unqualified person may result in water leakage, power leakage, system breakdown, or fire.
1. Installation information Installation information 1-2. Precautions for Indoor unit, Hydro unit, and HBC controller 1-2-1. Operating environment If the refrigerant leaks, the oxygen level may drop to harmful levels. If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant leaks.
1. Installation information Installation information 1-3. Precautions for outdoor unit/heat source unit 1-3-1. Installation environment The outdoor unit with the salt-resistant specification is recommended for use in an area in which it will be exposed to salt air. Even when the unit with the salt-resistant specification is used, it is not completely protected against corrosion. Be sure to follow the directions or precautions described in the Instruction Book and Installation Manual for installation and maintenance.
1. Installation information Installation information 1-4. Precautions for control-related items 1-4-1. Product specification To introduce the MELANS system, a consultation with us is required in advance. Especially to introduce the electricity charge-apportioning function or energy save function, further detailed consultation is required. Consult your local distributor for details.
Page 63
CONTENTS Caution for refrigerant leakage for R410A Caution for refrigerant leakage for R410A I.Caution for refrigerant leakage for R410A 1. Caution for refrigerant leakage for R410A ....................2 1-1. Refrigerant property ......................... 2 1-2. Confirm the Critical concentration and take countermeasure ............2 MEES19K170...
Page 64
Note 1. Countermeasure 3 should be done in a proper way in which the fresh air supply shall be on whenever the leakage happens. Note 2. In principle, MITSUBISHI ELECTRIC requires proper piping design, installation and air-tight testing after installation to avoid leakage happening.
Page 65
- Doing so may cause the unit or pipes to burst, or result in explosion or fire during use, repair, or at the time of disposal of the unit. - It may also be in violation of applicable laws. - MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong type of refrigerant.
Need help?
Do you have a question about the CITY MULTI HYBRID and is the answer not in the manual?
Questions and answers