Frequency setting
1) Setting the frequency using potentiometer
MAX
MIN
[Parameter setting]
Set the "basic parameter frequency setting mode selection 1" parameter  to .
3
(There is no need to set this parameter before the first use after purchase.)
2) Setting the frequency using input voltage (0~10V)
+
-
[Parameter setting]
Set the "basic parameter frequency setting mode selection 1" parameter  to .
(There is no need to set this parameter before the first use after purchase.)
3) Setting the frequency using current input (4(0)~20mA)
+
-
[Parameter setting]
Set the "extended parameter analog input VI/II voltage/current switching"
parameter  to .
In addition, set the "basic parameter frequency setting mode selection 1" parameter
 to .
To bring the operation frequency to 0Hz at an input current of 4mA, set the "VI/VII input
point setting 1" parameter  to .
PP
:Frequency settings
RR/S4
With potentiometer
CCA
RR/S4
:Voltage signal 0-10Vdc
CCA
VI/II
:Current signal 4(0)-20mAdc
CCA
Potentiometer
The operation frequency by potentiometer (1~10kΩ- 1/4W ) for setting
⇒ Refer to Section 7.3 for details of adjustment.
60Hz
Frequency
Voltage signal
Voltage signal (0~10V) for setting the operation frequency
⇒ Refer to Section 7.3 for details of adjustment.
60Hz
Frequency
Current signal
Current signal (4(0)~20mA) for setting the operation frequency
⇒ Refer to Section 7.3 for details of adjustment.
Frequency
C-4
0
MIN
MAX
0
10Vdc
0Vdc
60Hz
0
4mAdc
20mAdc
E6581386