Toshiba VF-PS1 Instruction Manual page 101

Variable torque inverter
Hide thumbs Also See for VF-PS1:
Table of Contents

Advertisement

All 200V VF-PS1 and 400V VF-PS1 with ratings of up to 220kW have built-in dynamic braking transistors as standard
equipment. If the rating of your inverter falls within this range, connect the resistor, as shown in Figure a) below or
Figure b) on the next page. If your inverter has a power rating of 250kW or more, connect a resistor, as shown in
Figure c).
Connecting an external braking resistor (optional)
a) External braking resistor (with a thermal fuse) (optional)
MCCB
Three-phase
main circuit
Power supply
[Parameter setting]
Title
Function
Dynamic braking selection

Do not connect an external resistor with a resistance (combined resistance) smaller than the minimum admissible
resistance.
For overload protection, be sure to set the parameters  and  properly.
[Parameter setting]
Title
Function
Dynamic braking resistance

Allowable continuous braking

resistance
Braking resistance overload

time
An external braking resistor
(optional)
PA/+
PB
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
Inverter
Adjustment range
:Disabled
:Enabled (braking resistance
overload detect)
:Select (braking resistance overload
not detect)
Adjustment range
~ Ω
~ kW
~ sec.
E-35
E6581386
Motor
IM
Example of setting
Example of setting
Any value
Any value
Set the parameter to
 for type PBR*- or to
any value for other
types.
5