Minimum resistance of connectable braking resistors
The minimum allowable resistance values of the externally connectable braking resistors are listed in the table
below.
Do not connect braking resistors with smaller resultant resistance than the listed minimum allowable resistance
values.
(For 250kW or greater models, a dynamic braking resistor drive unit (optional separate unit) is needed.)
Inverter
Related output capacity
Resistance of
(kW)
standard option
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
220
250
280
315
400
500
630
200V Class
Minimum allowable
resistance
200Ω
50Ω
200Ω
50Ω
75Ω
35Ω
75Ω
20Ω
40Ω
16Ω
20Ω
11Ω
15Ω
8Ω
10Ω
5Ω
7.5Ω
5Ω
7.5Ω
3.3Ω
3.3Ω
3.3Ω
3.3Ω
2.5Ω
2Ω
1.7Ω
2Ω
1.7Ω
2Ω
1.7Ω
1.7Ω
1.3Ω
1.7Ω
1Ω
E-39
400V Class
Resistance of
Minimum allowable
standard option
resistance
200Ω
200Ω
200Ω
160Ω
80Ω
60Ω
40Ω
30Ω
13.3Ω
30Ω
13.3Ω
15Ω
13.3Ω
13.3Ω
8Ω
6.7Ω
8Ω
8Ω
8Ω
3.3Ω
3.7Ω
2.5Ω
3.7Ω
1.9Ω
3.7Ω
1.9Ω
3.7Ω
1.9Ω
1.9Ω
1.9Ω
1.4Ω
1.4Ω
1.4Ω
0.95Ω
0.7Ω
0.7Ω
0.7Ω
0.7Ω
0.7Ω
E6581386
60Ω
60Ω
60Ω
40Ω
30Ω
20Ω
20Ω
5
10Ω
5Ω
5Ω
1Ω
1Ω
1Ω