Signal Transmission Error; (Between Main Remote Controller And Sub Remote Controller); Signal Transmission Error (Between Main Remote Controller And Sub Remote Controller) - Daikin 3MKS50E3V1B Service Manual

Super multi nx e / f / g / k-series
Hide thumbs Also See for 3MKS50E3V1B:
Table of Contents

Advertisement

Troubleshooting for SA Indoor Unit - FCQG, FFQ, FHQ, FDBQ, FBQ Series
6.9
Signal Transmission Error (between MAIN Remote
Controller and SUB Remote Controller)
U8
Remote
Controller
Display
Method of
In case of controlling with 2 remote controllers, check the system using micro-computer if signal
Malfunction
transmission between indoor unit and remote controller (main and sub) is normal.
Detection
Malfunction
Normal transmission does not continue for specified period.
Decision
Conditions
Supposed
Causes
Troubleshooting
294
Remote controller is set to "SUB" when using 1 remote controller
Connection of 2 sub remote controllers (when using 2 remote controllers)
Defective remote controller PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
NO
Using 2 remote
controllers?
YES
Is SS1 of both
NO
remote controllers
set to "SUB"?
YES
Is SS1
NO
of remote
controller PCB set to
"SUB"?
YES
SiBE121135
Set SS1 to "MAIN"; turn the
power supply off once and then
back on.
Turn the power off and then
back on. If a malfunction occurs,
replace the remote controller
PCB.
Set one remote controller to
"MAIN"; turn the power supply
off once and then back on.
(R15321)
Service Diagnosis