SiUS12-928_A
5.7
Signal Transmission Error (between Indoor and Outdoor
Units)
U4
Remote
Controller
Display
Method of
The data received from the outdoor unit in indoor unit-outdoor unit signal transmission is checked
Malfunction
whether it is normal.
Detection
Malfunction
The data sent from the outdoor unit cannot be received normally, or the content of the data is
abnormal.
Decision
Conditions
Defective outdoor unit PCB
Supposed
Defective indoor unit PCB
Causes
Wiring error
Disturbed power supply waveform
Breaking of the connection wires between the indoor and outdoor units (wire No. 3)
Service Diagnosis
Troubleshooting
110