Field Settings
BRC1E52A7, BRC1E52B7
a
a Unit No.
b First code No.
c Second code No.
d Mode
420
d
Step
Action
1
Press and hold the [Cancel] button (
for 4 seconds to enter the Field setting
menu.
2
Use the
buttons to select Field setting
list and push the [Menu/Enter] button (
3
Use the
buttons to select the desired
Mode.
4
During group control, when setting by each
indoor unit (Mode 20, 21, 22 and 23 have
been selected), push the
highlight and
INDOOR UNIT NO. to be set. This operation
is unnecessary when setting by group.
5
Highlight the second code No. to be changed
using the
buttons, and use the
buttons to select the desired second code No.
6
Push the [Menu/Enter] button (
display the confirmation screen.
7
Use the
buttons to select Yes and push
the [Menu/Enter] button (
8
Push the [Cancel] button (
return to basic screen.
c
(R12878)
)
).
button to
buttons to select the
) to
).
) 2 times to
Remote controller
(R12879)
When setting by group, all of the second
code No. that may be set are displayed
as "*".
When multiple setting changes are
needed, repeat steps 3 to 7.
Trial Operation and Field Settings
SiBE121135