Control Specification
4.7
Heating Peak-cut Control
Outline
During heating operation, the indoor heat exchanger temperature determines the frequency
upper limit to prevent abnormal high pressure.
Detail
A (°C)
B (°C)
C (°C)
D (°C)
E (°C)
114
The operating frequency is judged with the indoor heat exchanger temperature 2 minutes
after the operation starts and
The maximum value of the indoor heat exchanger temperature controls the following
(excluding stopped rooms).
B˚C
C˚C
D˚C
Indoor heat exchanger
thermistor temperature
Zone
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is canceled.
65
55
54
52
50
seconds after the number of operation room is changed.
F
Control
F (seconds)
When increase
When decrease
SiBE121135
Stop zone
A˚C
Dropping zone
Keep zone
Up zone
E˚C
Reset zone
(R14645)
30
2
Function and Control