Troubleshooting for Wall Mounted/Floor Standing Type
5.2
Freeze-up Protection Control/Heating Peak-cut Control
A5
Error Code
Method of Error
Freeze-up protection control
Detection
Heating peak-cut control
Error Decision
Freeze-up protection control
Conditions
Heating peak-cut control
Supposed
Short-circuited air
Causes
Clogged air filter of the indoor unit
Dust accumulation on the indoor heat exchanger
Defective indoor heat exchanger thermistor
Defective indoor unit PCB
Troubleshooting
Reference
Check No.01 Refer to P.224
158
During cooling operation, the freeze-up protection control (operation halt) is activated according
to the temperature detected by the indoor heat exchanger thermistor.
During heating operation, the temperature detected by the indoor heat exchanger thermistor is
used for the heating peak-cut control (operation halt, outdoor fan stop, etc.)
During cooling operation, the indoor heat exchanger temperature is below 0°C (32°F).
During heating operation, the indoor heat exchanger temperature is above 65°C (149°F).
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the air passage.
Is there any short circuit?
NO
Check the air filter.
Dirty?
NO
Check the dust accumulation on
the indoor heat exchanger.
Dirty?
NO
Check No. 01
Check the indoor heat exchanger
thermistor.
As
described in the
thermistor characteristic
chart?
YES
YES
YES
YES
NO
SiUS122226E
Provide sufficient air passage.
Clean the air filter.
Clean the indoor heat
exchanger.
Replace the indoor heat
exchanger thermistor.
Replace the indoor unit PCB
(control PCB).
(R21064)