10-3-4. Wiring Connection
u Connecting cable
Wiring the connecting cable can be carried
out without removing the front panel.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it
toward you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (or as according
to local regulations/codes) into the pipe hole
on the wall.
4. Pull the connecting cable through the cable
slot on the rear panel so that it protrudes
about 15 cm out of the front.
5. Insert the connecting cable fully into the
terminal block and secure it tightly with
screws.
Make a loop with the earth wire under the
terminal block and secure it with the earth
screw.
6. Tightening torque: 1.2 N•m (0.12 kgf•m)
7. Secure the connecting cable with the cord
clamp.
8. Attach the terminal cover and moving panel
on the indoor unit.
CAUTION
• Be sure to refer to the wiring system diagram
labelled inside the front panel.
• Check local electrical regulations for any specific
wiring instructions or limitations.
Termin l cov r
Screw
Screw
Cord clamp
Connecting cable
about 15 cm
10 mm
NOTE
• Connecting cable (Indoor unit/outdoor unit)
• Wire type: H07RN-F or 60245IEC66 (1.0 mm²)
– 81 –
Terminal block
Earth wire
Connecting cable
Fig. 10-3-6
Terminal block
Earth wire(loop)
Earth screw
Fig. 10-3-7
Fig. 10-3-8
Earth line
110 mm
10 mm
50 mm