Field Setting Switch Abnormality - Daikin Super Multi Plus E-Series FTXG25EV1BW Service Manual

Table of Contents

Advertisement

SiBE18-821_C

5.12 Field Setting Switch Abnormality

UA
Remote
Controller
Display
Method of
Malfunction
Detection
Malfunction
Incorrect field setting
Decision
Conditions
Supposed
Causes
Troubleshooting
Turn the power supply off
once, and back on to restart.
Troubleshooting
Incorrect wiring between indoor unit and BP unit
Incorrect wiring of remote controller
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Is the remote
YES
controller connected to
one or more indoor
units?
NO
Is the remote
YES
controller wiring jumped
between indoor
units?
NO
NO
Is the field
setting correct?
YES
Do the
microcomputer
NO
normal monitors HAP on all
indoor unit PCB
blink?
YES
NO
Does the system conduct
normal operation?
YES
Troubleshooting for SA Indoor Unit
Are the wirings
NO
between indoor unit and
BP unit correctly
connected?
YES
Is 220 ~ 240
YES
VAC between No.1 and
3 of X2M terminal
(indoor unit)?
NO
Are the wirings
NO
between indoor unit and
BP unit correctly
connected?
YES
Connect the remote controller
correctly.
Remove the jumper.
Set it correctly.
Connect them correctly.
Check the power supply system
inside the indoor unit.
Could be incorrect wiring.
Check again.
Connect them correctly.
Replace the indoor unit PCB.
Normal
(R13011)
375