SA Indoor Unit - FFQ, FCQ, FDBQ, FBQ, FHQ Series
Set temp mode changeover
Limit Operation
Limit operation provides thermostat control within the range of the set minimum and maximum temperature.
The minimum temperature setting will trigger heating. The maximum temperature setting will trigger cooling.
Operation Method
1
Basic screen
2
3
English
284
The limit operation can not be enabled when a centralized control is connected.
• Display the main menu screen.
(See page 26.)
• Press
buttons to select "Set
temp mode changeover" on the
main menu screen.
• Pressing Menu/Enter button takes
you back to the basic screen, and
the set temperature is displayed in
max °C min °C.
* To return to the normal set temperature
screen, use "Set temp mode changeover"
in the Main Menu again.
• To change the set temperature,
press
buttons.
The set temperature is highlighted
and ready to be changed.
• The set temperature will increase by
1°C when the
and decrease by 1°C when the
button is pressed.
Note
• The difference between the maximum and minimum
temperatures cannot be set to less than 6°C.
(* Maximum temperature – Minimum temperature ≥ 6°C)
• Pressing
variable set temperature between
max. and min.
(Limit Operation)
button is pressed