RAV-SM1400UT-E, RAV-SM1400AT-E, RAV-SM1401BT-E, RAV-SM1401CT-E, RAV-SP1400AT-E
Outer diameter of refrigerant pipe
Gas side ØA
Liquid side ØB
15.9mm
9.5mm
TD sensor
Accumulator
Rotary
(2500cc)
compressor
(DA420A3F – 21M)
Pressure
(MPa)
Pd
Standard
3.3
Cooling
Overload
3.5
Low load
1.7
Standard
3.0
Heating
Overload
3.4
Low load
2.0
4 poles are provided to this compressor.
*
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
Refrigerant pipe
at gas side
Outer dia. ØA
Ball valve
Outer dia. ØA
Strainer
TS sensor
Check joint
4-way valve
(STF-0213Z)
Heat exchanger Ø8
Muffler
1 row 52 stages
FP1.3 flat fin
Ø25 × L210
Ø25 × L180
Pipe surface temperature (°C)
Discharge
Suction
Ps
(TD)
(TS)
0.9
84
11
1.0
87
7
0.8
44
8
0.6
79
2
1.1
78
21
0.2
82
–21
RAV-SM1400UT-E, RAV-SM1400AT-E, RAV-SM1401BT-E
RAV-SM1401CT-E, RAV-SP1400AT-E
Indoor unit
TCJ sensor
Strainer
Air heat exchanger
Outdoor unit
TO sensor
TE sensor
Indoor heat Outdoor heat
revolutions per
exchanger
exchanger
(TC)
(TE)
10
40
15
54
4
8
44
2
54
17
36
–18
– 38 –
Distributor
(Strainer incorporated)
TC sensor
Refrigerant pipe
at liquid side
Outer dia. ØB
Packed valve
Outer dia. ØB
PMV
(UKV-25D22)
Strainer
Distributor
R410A 2.3kg
Indoor/Outdoor
Compressor
temp. conditions
Indoor
(DB/WB) (°C)
fan
second (rps)
*
Indoor
56
HIGH
27/19
54
HIGH
32/24
27
LOW
18/15.5
60
HIGH
20/–
24
LOW
30/–
73
HIGH
15/–
Min.
Max.
5m
50m
Cooling
Heating
Outdoor
35/–
43/–
–5/–
7/6
24/18
–20/
(70%)