Toshiba RAV-SP560AT-E Service Manual page 173

Split type
Hide thumbs Also See for RAV-SP560AT-E:
Table of Contents

Advertisement

No.
Part name
1. Detachment
Drain pan
1) Perform works of items 1 of
2) Remove clamps of the lead wires con-
NOTE :
Remove the connector by releasing locking
of the housing.
3) Remove screws fixing earth lead wire in
4) Remove indoor/outdoor inter-unit cable
5) Remove screws fixing the electric parts
6) Remove screws fixing the bell mouth.
7) Remove the drain cap, and drain water
NOTE 1 :
When removing the drain cap, be sure to
prepare a bucket to catch the drained water.
NOTE 2 :
Thermal insulator is adhered to the drain
cap. Be careful not to peel off the insulator.
If the insulator has been peeled, adhere it
with double-face tape, etc. as before.
8) Remove screws fixing the drain pan.
2. Attachment
1) Fix the parts, drain cap, drain pan, bell
2) Connect connectors, earth lead wire,
Procedure
ƒ
of
and 1 of
.
nected to the following connectors of the
control P .C. board.
CN34
: Float switch (3P: Red)
CN68
: Drain pump (3P: Blue)
CN101 : TC sensor (2P: Black)
CN102 : TCJ sensor (2P: Red)
CN333 : Power supply of fan motor
(5P: White)
CN334 : Position detection of fan motor
(5P: White)
the electric parts box. (Ø4 x 6, 2 pcs.)
and remote controller cable of the termi-
nal block.
box. (Ø4 x 10, 5 pcs.)
(Ø4 x 10, 6 pcs.)
accumulated in the drain pan.
(Ø4 x 8, 4 pcs.)
mouth, and electric parts box succes-
sively to their original positions.
indoor/outdoor inter-unit cable, and
remote controller cable which have been
disconnected in the above item 1 as
before.

, 1 of
, 1
– 173 –
RAV-SM560/800/1100/1400UT-E
RAV-SP1100UT-E
Remarks
Screws fixing earth lead wires
Drain cap
Screws fixing drain pan

Hide quick links:

Advertisement

Table of Contents
loading