No.
Part name
1. Detachment
Adjust corner
cap
2. Attachment
1. Detachment
Ceiling panel
2. Attachment
Procedure
1) Perform work of item 1. of
2) Remove screws at 4 corners of the
suction port. (Ø4 x 10, 4 pcs.)
3) Push the knob outward and remove the
adjust corner cap by sliding it.
1) Mount the adjust corner cap by sliding
it inward.
2) Tighten screws at 4 corners of the
suction port. (Ø4 x 10, 4 pcs.)
1) Perform works of items 1 of
and 1 of
.
2) Remove the flap connector (CN33,
White, 5P) connected to the control P .C.
board, and then remove the lead wire
from the clamp.
NOTE :
Remove the connector by releasing
locking of the housing.
3) Remove screws fixing the ceiling panel.
(M5, 4 pcs.)
4) Push the tentative hook outward to
remove the ceiling panel.
1) Hang the tentative hook of the main
body drain pan to the tentative hook of
the ceiling panel.
NOTE :
A panel has directional property, so mount
a panel with attention to the marks.
2) Tighten fixing screws. (M5, 4 pcs.)
3) Connect flap connector of the ceiling
panel to connector (CN33, White, 5P)
on the control P .C. board.
.
, 1 of
Remove the flap
connector
– 170 –
RAV-SM560/800/1100/1400UT-E
RAV-SP1100UT-E
Remarks
Screw
Push outward
Fixing screw
Push the tentative
hook outward