Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
[P29 error]/[16 error]
Are connections of
cable/connector normal?
YES
Is compressor normal?
YES
[H03 error]/[17 error]
Are cablings of power and
current sensor normal?
YES
Check IPDU.
Defect
Replace
NO
NO
Is not earthed?
NO
Is not winding shorted?
(Is resistance between windings 0.6 to 1.2 ?)
NO
Is not winding opened?
NO
Check IPDU P.C. board.
Defect
Replace
NO
* For RAV-SM560AT-E, replace control P.C. board.
www.ilmalämpöpumput.com
YES
YES
YES
* For RAV-SM560AT-E, replace control P.C. board.
– 80 –
Check and correct circuit cabling
such as cabling to compressor.
Compressor error
Replace
Compressor error
Replace
Compressor error
Replace
Check and correct circuit cables.