No.
Part name
X
1. Detachment
Drain pump
assembly
3. Attachment
NOTE :
The drain pump is fixed with a hook and 3
screws. In screwing, be sure that screws
do not to run on hooking claw at the main
body side.
NOTE :
Insert the drain hose up to the end of
pump connecting part, and bind the white
mark position of the hose with band.
Procedure
1) Perform works of items 1 of
S
T
1 of
, 1 of
and 1 of
2) Picking the hose band, slide it from
pump connecting part to remove the
drain hose.
3) Remove screw fixing the drain pump
assembly, slide hooking claws of the
drain pump assembly and the main
body (1 position), and then remove the
assembly. (Ø4 x 8, 3 pcs.)
1) Fix the drain pump assembly as before.
2) Attach the drain hose and hose band
as before.
www.ilmalämpöpumput.com
Q
R
, 1 of
,
W
.
– 140 –
Remarks
Slide to hose side.
Hose band
Pump connecting part
Hooking claw
Fixing screw