Toshiba RAV-SM560AT-E Service Manual page 78

Toshiba hfc r410a split type air conditioners service manual
Hide thumbs Also See for RAV-SM560AT-E:
Table of Contents

Advertisement

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
[P19 error]/[08 error]
NO
Check and replace
electron expansion
valve.
NO
* Refer to Characteristics-2.
Replace TC sensor.
• In cooling operation, if high pressure is abnormally raised, [P19 error]/[08 error] may be displayed. In this
case, remove cause of pressure up and then check again referring to the item [P04 error]/[21 error].
[F02 error]/[0d error]
Is connection of TC sensor connector
(Indoor P.C. board CN101) normal?
YES
Are characteristics of
TC sensor resistance value normal?
YES
Check indoor P.C. board
(MCC-1402).
Defect
Replace
NO
Is operation of
4-way valve normal?
YES
Is flow of refrigerant
by electron expansion
valve normal?
YES
Are characteristics
of TC sensor resistance
value normal?
YES
Check indoor P.C. board.
Defect
Replace
NO
NO
* Refer to Characteristics-2.
www.ilmalämpöpumput.com
Is voltage applied
to 4-way valve coil terminal
in heating operation?
YES
Is circuit cable normal?
YES
Check CDB P.C. board.
YES
* For RAV-SM560AT-E, check control P.C. board.
– 78 –
NO
Check 4-way valve
Defect
Replace
NO
Check and correct circuit.
NO
Check CDB P.C. board.
Defect
Replace
Correct connection of connector.
Replace TC sensor.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents