Toshiba RAV-SM560AT-E Service Manual page 54

Toshiba hfc r410a split type air conditioners service manual
Hide thumbs Also See for RAV-SM560AT-E:
Table of Contents

Advertisement

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
No.
Item
Louver control
9
1) Louver
position
2) Air direction
adjustment
(Swing
operation)
10
Frequency fixed
operation
(Test run)
Outline of specifications
The louver angle is displayed
setting 0° as "Full close".
1) In the initial operation after
power-ON, the position is
automatically controlled according to the operating
status (COOL/HEAT).
Cooling
45
2) After then a louver position is stored in the microcom-
puter every time when position is operated on the
remote controller, and the louver operates at the position
stored in memory in the next operation and after.
* If the operation mode has been changed from COOL
to HEAT, from HEAT to COOL, or the power has
turned off, the stored louver position is cleared and
the status returns to one in item 1).
1) When pushing [LOUVER] button during operation, the
louver starts swinging.
2) When the louver has arrived at the desired position, push
[LOUVER] again. The louver stops at that position.
1) In case of wired remote controller
1. When pushing [ON/OFF] button on the remote
controller continuously for 5 seconds, the mode
enters [TEST]. The indoor fan rotates with [HIGH]
and a frequency fixed operation starts.
2. During this operation, the buttons other than [ON/
OFF], [UP
] and [DOWN
However, items 7 and 8 are effective.
3. To stop the frequency fixed operation, use [ON/OFF]
button only.
2) In case of wireless remote controller (Without wired
remote controller)
1. When pushing [Temporary] button continuously for
10 seconds or more, "Pi" sound is heard and the
mode enters [TEST]. The indoor fan rotates with
[HIGH] and a frequency fixed operation of [COOL]
starts.
NOTES :
• Temporary button is provided to near the display part of
the main unit when opening the front panel.
• If [Temporary] button is not continuously pushed for 10
seconds, "Automatic heating/cooling operation" is
performed.
2. To stop the operation, push [Temporary] button again.
NOTE :
Operation on the wireless remote controller is not ac-
cepted.
www.ilmalämpöpumput.com
Full close
0
Heating
103
] cannot be accepted.
– 54 –
Remarks
[COOL]/[HEAT] flash.
Air volume: [AUTO]
Temperature
COOL: [L]
HEAT: [H]
Commanded frequency
Approximately [S7]

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents