[0d error]
Is connection of TC sensor connector
(Indoor P.C. board CN05) normal?
YES
Are characteristics of
TC sensor resistance value normal?
YES
Check indoor P.C. board
(MCC-1370A).
Defect
Replace
[0F error]
Is connection of TCJ sensor connector
(Indoor P.C. board CN20) normal?
YES
Are characteristics of
TCJ sensor resistance value normal?
YES
Check indoor P.C. board
(MCC-1370A).
Defect
Replace
NO
NO
* Refer to Characteristics-2.
NO
NO
* Refer to Characteristics-2.
– 124 –
www.ilmalämpöpumput.com
Correct connection of connector.
Replace TC sensor.
Correct connection of connector.
Replace TCJ sensor.