[F01 error]/[0F error]
Is connection of TCJ sensor connector
(Indoor P.C. board CN102) normal?
YES
Are characteristics of
TCJ sensor resistance value normal?
YES
Check indoor P.C. board
(MCC-1403).
Defect
Replace
[P26 error]/[14 error]
Is power voltage normal?
Are connections of
cabling/connector normal?
YES
Does RY01 relay of
IPDU operate?
YES
Is not AC fuse fused?
Replace IPDU.
* Replace control P.C. board
of RAV-SM560AT-E.
Check IPDU.
Defect
NO
NO
* Refer to Characteristics-2.
NO
YES
NO
* For RAV-SM560AT-E,
check RY01 on the control P.C. board.
YES
NO
* Single-phase type is not
provided to RAV-SM560AT-E.
NO
Replace
www.ilmalämpöpumput.com
Check and correct circuit cables.
Correct connection of connector.
Check and correct reactor connection.
Are not "P26" and "14" errors output
when an operation is performed by
removing 3P connector of compressor?
YES
Is compressor normal?
YES
Check rare short of compressor trouble.
Defect
– 79 –
Correct connection of connector.
Replace TCJ sensor.
Improve the power supply line.
NO
Replace IPDU.
* Replace control P.C. board
of RAV-SM560AT-E.
NO
Replace