5.4

INITIALIZE MODE

As described below, the language displayed on the digital operator, the access level to set/read
constants or control method (V/f control, vector control) can be selected. Set constants A1−01 and
A1−02 before use of the VS−616G5. The following table shows the main constants for initialize
mode.
Table 20
Con−
stant
No.
A1−00
A1−01
A1−02
:
A1−03
:
A1−04
A2−01
to
A2−32
Initialize Mode
Digital Operator Display
Language selection
Select Language
(change enable during
run)
Access level
(change enable during
Access Level
run)
Control Method
Control method selection
Init Parameters
Reset to factory defaults.
Enter Password
Password
User Param 1 to 32
User setting constant
:
Do not set the constants unnecessarily, or the constants are initialized (A1−03) or some
constants cannot be changed (A1−04).
5
SETTING OPERATION CONDITIONS
Name
0 : English
1 : Japanese
0 : Exclusive for monitoring
1 : Constants for user selection
(Constants to be set/read can be programmed by
operator.)
2 : QUICK−START
(Constants required for test run are set/read.)
3 : BASIC
(Normally−used constants are set/read.)
4 : ADVANCED
(All constants are set/read.)
0 : V/f control
1 : V/f control with PG feedback
2 : Open loop vector
3 : Flux vector
0
: No Initialization
1110
: Initialization of user setting
2220 : 2−wire initialization
3330 : 3−wire initialization
Password setting
When A1−01=1 (user program) is selected, selects the
constants that can be set/read by digital operator.
Description
51