3.4

CONFORMATION TO EMC STANDARDS

In order to coform to EMC standards, the exclusive−use methods are required for line filter application,
cable shielding and inverter installation. The following explains the outline of the methods.
The line filter and the inverter must be mounted on the same metal plate. The filter should be mounted
as close to the inverter as practical. Keep cable as short as possible. The metal plate should be securely
grounded. The ground of line filter and inverter must be bonded to the metal plate with as much area
as possible.
For mains input cable, screened cable is recommended at least within the panel. The screen of the cable
should be connected to a solid ground. For the motor cable, screened cable (max. 20 m) must be used
and the screen of the motor cable is connected to ground at both ends by a short connection, using as
large an area as practical.
For more detailed explanation, refer to "Making YASKAWA Inverter Products Conform with EMC
Directive" (EZZ006908).
The following table and figures show the line filter list for EMC standards and the installation/wiring
of inverter and line filter.
32
Table 10
Line Filter List for EMC Standards
Inverter Model
Inverter Model
CIMR−G5C
51P5
52P2
53P7
55P5
57P5
5011
5015
Line Filter (manufactured by Schaffner)
Rated
Model
Current (A)
FS5492−18−07
18A
FS5492−42−07
FS5492−42−07
42A
42A
Dimensions in mm
Mass (kg)
W×D×H
2.4
70×329×185
4.2
4 2
100×389×185
100×389×185