Table 4: Installer Configuration Menu (Part 4 of 4)
Parameter
Description and Default
Appearing
on Display
Cal RS
Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0C°/0.0C°F
Cal OS
Sets the desired outdoor air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0C°/0.0F°
H stage
Reverts the operation of a two-stage
thermostat controller to a
single-stage thermostat controller
when the second heating stage is
not needed.
Default: 2.0
C stage
Reverts the operation of a two-stage
thermostat controller to a
single-stage thermostat controller
when the second cooling stage is
not needed.
Default: 2.0
H lock
Discontinues heating operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: 49°C/120°F
C lock
Discontinues cooling operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: -40°C/-40°F
Aux cont
Energizes peripheral devices
(lighting equipment, exhaust fans,
and economizers).
Default: n.o.
1.
When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and
hold the UP or DOWN arrow key to change the numeric value in increments of ten.
2.
When adjusting the temperature, press the UP or DOWN arrow key to change the value in 0.5F°/0.5C° increments; press
and hold the UP or DOWN arrow key to change the value in 5.0F°/5.0C° increments.

Programming the Thermostat Controller

After configuring the thermostat controller by means of
the Installer Configuration Menu, program its operating
parameters by means of the Main User Menu. Access
this menu by pressing the MENU key during normal
operation. The Main User Menu contains the basic
operating features of the thermostat controller.
TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions
Selection Options
Range: -2.5C°/-5.0F° to 2.5C°/5.0F° adjustable in 0.5C°/1.0F°
increments
Range: -2.5C°/-5.0F° to 2.5C°/5.0F° adjustable in 0.5C°/1.0F°
increments
(1.0): One Stage
(2.0): Two Stages
(1.0): One Stage
(2.0): Two Stages
Range:-26°C/ -15°F to 49°C/120°F adjustable in 5C°/5F°
increments
Range: -40°C/-40°F to 35°C/95°F adjustable in 5C°/5F° increments
(n.c.): Contact open = Occupied; contact closed = Unoccupied.
(n.o.): Contact closed = Occupied; contact open = Unoccupied.
The contact toggles with the internal Occupied/Unoccupied
schedule (or the NSB contact on one of the digital inputs, if used).
The Main User Menu also uses Auto Help, which is
displayed automatically in the menu when there is a
pause in programming activity. To exit Auto Help,
continue with the programming selection. When the
thermostat controller is in the Main User Menu and is
left unattended for 45 seconds, the menu reverts to the
Status Display Menu.