Vent Requirements

!
Always maintain the required 1" clearance (air space) to combustible materials to prevent a fire
hazard. Do not fill air spaces with insulation.
!
The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance.
¥
Minimum 5' vertical rise
from top of stove
¥
When the vent passes
through a wall, a wall
thimble is required.
When the vent passes
through a ceiling, a
support box or firestop is
required. When the vent
passes through the roof,
a roof flashing and storm
collar are required.
Follow the instructions
and requirements
provided with the vent
when installing.
¥
The horizontal run may
not exceed 50% of the
vertical rise
¥
Use 4" dia. B vent for entire system from one manufacturer (don't mix brands)
Use high temperature factory built or masonry chimney with listed gas chimney liner running the
entire length
¥
Vent termination must be above the roof and not below any eaves or overhangs
Drafting
This appliance relies upon natural draft to operate. External forces, such as wind,
Performance
barometric pressure, topography, or factors of the home (negative pressure from exhaust
fans, chimneys, air infiltration, etc.), may adversely affect draft. Travis Industries can
not be responsible for external forces leading to less than optimal performance.

Vent Termination Requirements

¥
Vent termination must have an approved cap (to prevent water from entering)
¥
Vent termination must not be located where it will become plugged by snow or other material
¥
Vent termination must be
1' above the roof and
meet the requirements
outlined in ANSI
Z223.1, section 7.6.2.
!
When installed, the vent must provide suitable draft for the appliance. Other factors, such as exhaust
fans, may create negative pressure inside the home and cause down drafts. Additional vent height
may be required in these circumstances.

Electrical Connection

¥
Plug the power cord into a grounded 110 Volt outlet (do not remove the grounding plug).
I
NSTALLATION
Min. 5' Rise
Standard Installation
12Ó Min.
(C
.) -
ONT
For qualified installers only!
Vent must
terminate a
minimum 1'
above the roof.
Maintain 1"
minimum
clearance
Provide a 1/4" rise
for every 12" run.
Type B Vent
Exterior Vent
- or -
Note: ANSI 223.1, section 7.6.2 outlines additional
requirements for gas vent terminations. If your
installation involves a roof with a slope greater
than 6/12 or if a wall or other vertical obstruction is
within 8' of the vent termination, the vent
termination will need to be taller. Refer to ANSI
223.1 for full details.
Do not block gas
vent termination
Min. 5' Rise
High
temperature
factory built
chimney and
connector
Listed Gas
The total
Chimney Liner
horizontal
run must
not exceed
50% of the
vertical rise
Chimney with Liner