Freeze Cylinders Manual Or Automatic Defrost Systems; Manual Defrost System; Automatic Defrost System; Sleep'' (Sleep Time) - Cornelius FCB 3 H.P. POST-MIX DISPENSER Installation & Service Manual

Two-flavor w/hot-gas defrost and v3+ features
Table of Contents

Advertisement

''DEFROST 1'' or ''DEFROST 2'' Display Messages.
''DEFROST 1'' or ''DEFROST 2'' display messages will appear on message display if either freeze cylinder is in
defrost mode. ''DEFROST 1'' or ''DEFROST 2'' messages will remain on during defrost cycle and will disappear
when cycle has ended.
''POINT OF SALE'' Display Message.
Three ''POINT OF SALE'' display messages are available to choose from and may be programmed into Unit as
instructed to appear on message display.
Common Outlet Temperatures.
Evaporator refrigeration coils inlet 1 and inlet 2 and common outlet temperatures may be displayed on control
panel message display as instructed.

FREEZE CYLINDERS MANUAL OR AUTOMATIC DEFROST SYSTEMS

The Unit is equipped with both manual and automatic hot-gas defrost systems. The automatic defrost system
may be programmed into the Unit to occur up to nine different times a day with a minimum of two hours
between defrost time settings or the system may be completely turned off.

MANUAL DEFROST SYSTEM

The Manual hot-gas defrost system may be activated at any time by pressing ''DEFROST'' switch on front of
the Unit. Refrigeration compressor will operate for a short time, then both freeze cylinders will go into defrost
and defrost for approximately 60-seconds. At end of manual defrost cycle, Unit will return to normal operation.
Manual defrost may be cancelled at any time by pressing ''CANCEL DEFROST'' switch.

AUTOMATIC DEFROST SYSTEM

The automatic hot–gas defrost system may be programmed into the Unit of occur up to nine different times a
day with a minimum of two hours between defrost settings. At start of each automatic defrost cycle, refrigeration
compressor will operate for 30-seconds to pump freon out of freeze cylinders evaporator coils. After freon has
been pumped out of freeze cylinders evaporator coils, No. 1 freeze cylinder only will go into defrost and defrost
for approximately 7-minutes then will return to normal operation. This ends automatic defrost cycle of No. 1
freeze cylinder. No. 2 freeze cylinder will defrost 30-minutes after the start of No. 1 freeze cylinder. The next
automatic defrost cycle will occur according to time programmed into the Unit.

''SLEEP'' (SLEEP TIME)

''SLEEP'' (SLEEP TIME( may be programmed into Unit to allow Unit to go into sleep time (Unit shut down,
freeze cylinders beaters and refrigeration systems not operating). At start of sleep time refrigeration compressor
will operate for 30-seconds to pump freon out of freeze cylinders evaporator coils. Then No. 1 freeze cylinder
will go into defrost for and defrost 60-seconds. After No. 1 freeze cylinder has defrosted, No. 2 freeze cylinder
will go into defrost and defrost for 60-seconds. At end of No. 2 freeze cylinder defrost, Unit will shut down and
go into sleep time.

''WAKE UP'' (WAKE UP TIME)

''WAKE UP'' (WAKE UP TIME) may be programmed into the Unit to allow Unit to resume normal operation at a
desired time. When programmed wake up time is reached, an alarm will sound for a short duration, then Unit
will resume normal operation.