Type
Terminal
S1
S2
S3
S4
S5
S6
S7
SC
RP
FS
FR
FC
MA
MB
MC
P1
P2
PC
AM
AC
190
Name
Multi-function input
selection 1
Multi-function input
selection 2
Multi-function input
selection 3
Multi-function input
selection 4
Multi-function input
selection 5
Multi-function input
selection 6
Multi-function input
selection 7
Multi-function input
selection common
Master reference
pulse train input
Power for frequency
setting
Master frequency ref-
erence
Frequency reference
common
NO contact output
NC contact output
Contact output
common
Photocoupler output 1
Photocoupler output 2
Photocoupler output
common
Analog monitor output
*2
Analog monitor
common
Function (Signal Level)
Factory setting closed:FWD run
open: Stop
Factory setting closed:REV run
open: Stop
Factory setting: External fault
(NO contact)
Factory setting: Fault reset
Factory setting: Multi-step speed
reference 1
Factory setting: Multi-step speed
reference 2
Factory Setting: JOG command
For control signal
33 kHz max.
+12 V (permissible current 20 mA max.)
0 to +10 VDC (20 kΩ) or 4 to 20 mA (250 kΩ) or 0 to 20
mA (250 Ω) (1/1000 resolution)
0 V
Factory setting: fault
Factory setting: Run
Factory setting: Frequency agree
0 V
Factory setting:
Output frequency
0 to +10 V
0 V
Photocoupler
insulation, 24
VDC, 8 mA
Contact capacity
*3
250 VAC 1 A or less,
30 VDC 1 A or less
Photocoupler
output +48 VDC,
50 mA or less
0 to +10 VDC, 2 mA or less,
8-bit resolution