Carrier Infinity ICS 58MVC 100 Series Installation Instructions Manual page 39

Direct vent 4-way multipoise condensing gas furnace
Hide thumbs Also See for Infinity ICS 58MVC 100 Series:
Table of Contents

Advertisement

NOTE:
Starting
at furnace,
slope
vent
pipe
a minimum
of
1/4-in.
(6 ram) per linear ft. back
toward
furnace
with
no sags
between
hangers.
VENT
TERMINATION
General
Combustion-air
(direct Vent / 2-pipe
system
only) and vent pipe
must terminate
outside
structure,
either through
sidewall
or roof.
For vent termination
clearance,
refer to Fig. 34 for Direct
Vent /
2-
Pipe
system
and
Fig.
35
for Ventilated
Combustion
Air
option.
Roof termination
is preferred
since it is less susceptible
to damage
or contamination,
and it has less visible
vent
vapors.
Sidewall
termination
require
sealing or shielding
of building
surfaces
with
a corrosive
resistance
material
due
to
corrosive
combustion
products
of vent system.
NOTE:
(Direct
Vent
/ 2-Pipe
system
ONLY)
A
factory
accessory
termination
kit MUST
be
used.
See
section
"Vent
Termination
Kit (Direct
Vent / 2-Pipe
System
Only)"
in this
instruction.
When determining
appropriate
location
for termination,
consider
the following
guidelines:
1. Comply
with all clearance
requirements
stated in Fig. 34
or Fig. 35 per application.
2. Termination
or termination
kit should
be positioned
where
vent vapors
will not damage
plants/shrubs
or air condi-
tioning
equipment.
3. Termination
or termination
kit should be positioned
so that
it will not be affected
by wind eddy, such as inside build-
ing corners,
nor by recirculation
of flue gases,
airborne
leaves, or light snow.
4. Termination
or termination
kit should
be positioned
where
it will not be damaged
by or subjected
to foreign
objects
such as stones,
balls, etc.
5. Termination
or termination
kit should
be positioned
where
vent vapors
are not objectionable.
Extended
Exposed
Sidewall
Pipes
Sidewall
combustion
air pipe termination
(direct
Vent / 2-pipe
system
only) and vent pipe termination
may be extended
beyond
area shown
in Fig. 36 or in Fig. 37 per application
in outside
ambient
by insulating
pipe as indicated
in Table 6.
1. Determine
combustion
air pipe
diameter
(direct
Vent
/
2-pipe
system
only)
and vent
pipe
diameter,
as stated
above,
using total pipe length
and number
of elbows.
2. Using
winter
design
temperature
(used
in load
calcula-
tions),
find
appropriate
temperature
for your
application
and furnace
model.
3. Determine
required
insulation
thickness
for exposed
pipe
length(s).
NOTE:
Pipe length
(ft / M) specified
for n_axinmm
pipe lengths
located
in unconditioned
spaces
cannot
exceed
total
allowable
pipe length as specified
in Table 6.
Vent Termination
Kit (Direct Vent / 2-Pipe
System
Only)
NOTE:
Always
refer to the instructions
in termination
kit for the
latest version.
Combustion
air and vent pipes MUST
terminate
outside
structure.
A factory accessory
termination
kit must be installed
as shown
in
Table
8.
There
are
four
options
of
vent/combustion
air
termination
kits available
as shown
in Table 8.
NOTE:
Combustion
air pipe must
have
the same
diameter
as
vent pipe.
Concentric
Vent / Combustion
Air Termination
Kit (Direct
Vent / 2-Pipe
System
Only
Determine
an appropriate
location
for termination
kit using
the
guidelines
provided
in section
"Vent
Termination:
General"
in
this instruction.
1. Cut one 4-in. diameter
hole for 2-in.
kit, or one 5-in. dia-
meter hole for 3-in. kit.
2. Loosely
assemble
concentric
vent/combustion
air termina-
tion components
together
using instructions
in kit.
3. Slide
assembled
kit with
rain shield REMOVED
through
hole.
NOTE:
Do not allow insulation
or other materials
to accumulate
inside of pipe assembly
when installing
it through
hole.
Roof
terminations-Locate
assembly
through
roof
to
appropriate
height
as shown
in Fig. 36 or Fig. 37.
Sidewall
terminations-Locate
assembly
through
sidewall
with
rain shield
positioned
no more
than
1-in
(25 ram).
from wall as shown in Fig. 36 and Fig. 37.
4. Disassemble
loose pipe fittings.
Clean
and cement
using
same procedures
as used for system
piping.
5. Check required
dimensions
as shown.
Two-Pipe
Termination
Kit (Direct
Vent / 2-Pipe
System
Determine
an appropriate location
for termination
kit using
the
guidelines
provided
in section
"Vent
Termination:
General"
in
this instruction.
1. Cut 2 holes,
1 for each pipe, of appropriate
size for pipe
size being used.
2. Loosely
install
elbow
in bracket
and place assembly
on
combustion-air
pipe.
Roof
terminations-Loosely
install
pipe
coupling
on
properly
cut vent
pipe. Coupling
nmst
be positioned
so
bracket
will mount
as shown
in Fig. 38.
For applications
using combustion-air
pipe option,
indic-
ated by dashed
lines in Fig. 36, install
90 ° street elbow
into 90 ° elbow, making
a U-fitting.
A 180 ° U-fitting
may
be used.
Sidewall
terminations-Install
bracket
as shown
in Fig.
36.
For applications
using vent pipe option
indicated
by dashed
lines
in Fig. 36, rotate vent elbow
90 ° from position
shown
in Fig. 36.
3. Disassemble
loose pipe fittings.
Clean
and cement
using
same procedures
as used for system
piping.
4. Check required
dimensions
as shown
in Fig. 36.
(Direct Vent / 2-Pipe
System
ONLY)-When
2 or more 58MVC
furnaces
are vented
near each other, 2 vent terminations
may be
installed
as shown
in Fig. 36, but next vent termination
must be at
least
36 in. (914
ram)
away
from
first
2 terminations.
It is
important
that vent terminations
be made as shown
in Fig. 36 to
avoid recirculation
of flue gases.
39

Advertisement

Table of Contents
loading

Table of Contents