Carrier Infinity ICS 58MVC 100 Series Installation Instructions Manual page 35

Direct vent 4-way multipoise condensing gas furnace
Hide thumbs Also See for Infinity ICS 58MVC 100 Series:
Table of Contents

Advertisement

AIR
INTAKE HOUSING
3/8" ID TUBE
3/16"
DRILL
TO OPEN
DRAIN
BURNER
BOX
_COMBUSTION
AIR PIPE
A93035
Fig. 40 - Intake
Housing
Plug Fitting
Drain
8. Install
casing
hole
filler
cap (factory-supplied
in loose
parts bag) in unused
combustion
air pipe casing hole.
Attachment
of Combustion
Air Intake
Housing
Plug Fitting
The
combustion-air
intake
plug
fitting
nmst
be
installed
in
unused
combustion
air intake
housing.
This
fitting
nmst
be
attached
by using
RTV sealant,
or by drilling
a 1/8-in.
hole in
fitting,
using
hole
in
intake
housing
as a guide.
Install
a
field-supplied
No. 6 or No. 8 sheet metal screw.
NOTE:
DO
NOT
OVER-TIGHTEN
SCREW.
Breakage
of
intake housing
or fitting may cause air leakage
to occur.
A plugged
drain connection
has been provided
on this fitting for
use when
moisture
is found
in combustion
air intake
pipe and
combustion
box.
If use of this drain
connection
is desired,
drill out fitting's
tap
plug with 3/16-in.
drill and connect
a field-supplied
3/8-in.
tube.
This tube should be routed
to open
condensate
drain for furnace
and A/C (if used), and should be trapped,
as shown
in Fig. 40.
NOTE:
(Direct
Vent
/ 2-Pipe
System
ONLY).
Moisture
in
combustion
air intake
may be a result
of improper
ternfination.
Ensure
combustion
air pipe
ternfination
is sinfilar
to those
as
shown
in Fig. 36 so that it will not be susceptible
to area where
light snow or others sources of moisture
could be pulled
in.
Combustion
Air Termination
- Ventilated
Combustion
Air
Option
Provisions
for adequate
combustion,
ventilation,
and dilution
air
must be provided
in accordance
with:
U.S. Installations:
Section
9.3 NFPA 54/ANSI
Z223.1-2006,
Air for Combustion
and Ventilation
and
applicable
provisions
of the local building
codes.
Canadian
Installations:
Part 8 of CAN/CS-B149.1-05.
Venting
Systems
and Air Supply
for Appliances
and all
authorities
having jurisdiction.
Combustion
air is piped
directly
to the burner
box
on furnace
using the same materials
used to vent the furnace.
(See Table 5.)
The combustion
air pipe is ternfinated
in an attic or crawl space
that is well ventilated
with OUTDOOR
AIR and is well isolated
from the living space or garage.
If the furnace
is installed
in a well
ventilated
attic, crawlspace
or other enclosure,
the combustion
air
pipe can be ternfinated
in the same space.
[]NIT
CORROSION
HAZARD
Failure
to follow
this caution
may result in reduced
furnace
component
life.
Air for combustion
nmst
not be contanfinated
by halogen
compounds,
which
include
fluoride,
chloride,
bronfide,
and
iodide.
These
elements
may
corrode
heat exchangers
and
shorten
furnace
life. Air contanfinants
are found
in aerosol
sprays,
detergents,
bleaches,
cleaning
solvents,
salts,
air
fresheners,
and other household
products.
The
combustion
air
pipe
cannot
be
ternfinated
in
attics
or
crawlspaces
that use ventilation
fans designed
to operate
during
the heating
season.
If ventilation
fans are present
in these areas,
the combustion
air pipe must ternfinate
outdoors
as a Direct Vent/
2-Pipe
system.
CARBON
MONOXIDE
POISONING
HAZARD
Failure
to follow
this warning
could
result
in personal
iniury or death.
The
operation
of exhaust
fans,
kitchen
ventilation
fans,
clothes
dryers,
attic exhaust
fans or fireplaces
could
create a
NEGATIVE
PRESSURE
CONDITION
at the
furnace.
Makeup
air MUST
be provided
for the ventilation
devices,
in addition
to that required
by the furnace.
Refer
to the
Carbon
Monoxide
Poisoning
Hazard
warning
at the end of
this section to deternfine
if an adequate
amount
of make-up
air is available.
NOTE:
Combustion
air pipe must
have
the same
diameter
as
vent pipe.
An attic or crawlspace
may
be considered
a space
that freely
communicates
with
the
outdoors
provided
there
are
adequate
permanent
ventilation
openings
directly
to outdoors
having
free
area of at least 1-in.2/4,000
Btuh of total input
rating for all gas
appliances
in the space.
NOTE:
In deternfining
the free area of an opening,
the blocking
effect of the louvers,
grilles,
and screens
nmst be considered.
If
the free area of a louver
or grille design
is unknown,
it may be
assumed
that wood
louvers
have a 20 percent
free area, and metal
louvers
or grilles have a 60 percent
free area. Screens,
when used,
must not be smaller
than l/4-in,
mesh.
Louvers
and grilles must
be constructed
so they cannot be closed.
CARBON
MONOXIDE
POISONING
HAZARD
Failure
to follow
this warning
could
result
in personal
iniury or death.
Many
homes
require
air to be supplied
from
outdoors
for
furnace
combustion,
ventilation,
and dilution
of flue gases.
The
furnace
combustion
air supply
must
be provided
in
accordance
with this instruction
manual.
g
Attic terminations
require
at least (1) 90 degree
elbow,
with the
open
end pointing
horizontally
or downward.
The open
end of
the elbow
must be at least 12-in.
(305 ram) above any insulation
35

Advertisement

Table of Contents
loading

Table of Contents