Facing Requirements - Travis Industries 35 CB Australian Owner's Manual

Direct vent fireplace
Table of Contents

Advertisement

10

Facing Requirements

Drywall may be butted up to the drywall standoff.
N O T E :
Drywall or other combustibles may not be placed over the drywall standoff.
N O T E :
No drywall or other combustible may protrude farther than 3/4" (19 mm) in front of the drywall
standoff. Any material that protrudes 3/4" (19 mm) or more from the drywall standoff must
meet the mantel clearance (if located above the fireplace) or sidewall clearance (if located to
the side of the fireplace.
HINT :
Holes are provided in the drywall standoff to attach the standoff to the framing members. This
stabilizes the standoff and allows the drywall to be anchored to the framing members.
No drywall or other combustible material
may protrude farther than 3/4" (19 mm)
in front of the drywall standoff. Any
material that protrudes 3/4" (19 mm) or
more from the drywall standoff must
meet the mantel clearance (if located
above the fireplace) or sidewall
clearance (if located to the side of the
fireplace.
Use the holes in the drywall standoff to
secure the standoff to the framing.
N O T E :
Mask off the front of the fireplace to keep drywall dust from entering the fireplace. These
particles, when heated, may cause odors or cause other problems.
Travis Industries
Installation
Maximum 3/4"
(19 mm)
(for qualified installers only)
Framing
Drywall
Standoff
9 3 5 0 8 1 3 4
Drywall
Min. 8-1/2" (216 mm) Clearance to
Combustibles (from edge of glass
frame)
4 0 3 0 6 2 4