Facing Requirements

The included fiber board is required and must remain attached to the fireplace (see "a" below).
Non-combustible facing must extend 7-3/4" (197mm) above the face of the fireplace (see "c" below).
Drywall or other combustible may not be place on top of this non-combustible area.
Drywall (or other combustible) may be placed above the non-combustible facing (see "a" below) and
to the sides and below the fireplace face. This combustible facing must be a minimum 7-3/4"
(197mm) above the face of the fireplace (see "b" below).
Tile or other non-combustible facing may be placed along the perimeter of the fireplace face, but
must not extend over it (see "d"). This area must remain open to allow for glass frame removal and
air flow.