Fireplace Placement Requirements; Minimum Framing Dimensions; Clearances - Travis Industries 35 CB Australian Owner's Manual

Direct vent fireplace
Table of Contents

Advertisement

Installation

Fireplace Placement Requirements

Minimum Framing Dimensions

The 1/2" (13 mm) stand-offs along the sides and back, and the 2-1/2" (64 mm) stand-offs on top of the
fireplace separate the fireplace from combustible materials (e.g.: combustible framing members,
plywood, sheetrock, paper-backed insulation). The stand-offs may contact the framing members but
no material may be placed between the stand-offs.
This fireplace may be placed in a bedroom. Please be aware of the large amount of heat this appliance
produces when determining a location.
42" Min.
(1067 mm)
The fireplace enclosure
must not be less than
42" (1067 mm) above
the base of the
fireplace.
If using a remote
control or thermostat,
route the wire to a
location near the gas
line (include an extra 3'
(1 Meter) length for
hookup).
Route the electrical line to a
position at the left front of
the fireplace.
Fireplace must be installed on a level surface capable of supporting the fireplace and vent
Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)
Due to the high temperature of the fireplace, it should be located out of traffic and away from furniture
and draperies.

Clearances

When installed, walls in front of the fireplace must be a minimum 8-1/2" (216 mm) to the side of the
fireplace facing (drywall standoff).
Fireplace must be placed so that no combustibles are within, or can swing within 36" (914 mm) of the
front of the fireplace (e.g. drapes, doors)
Fireplace must be placed so the vents below and above the glass do not become blocked
Travis Industries
(for qualified installers only)
32"
(813 mm)
16-7/8"
(429 mm)
39-7/8"
(1013 mm)
9 3 5 0 8 1 3 4
With an elbow directly off the top of the
fireplace, the vent is centerd 36" (914
mm) above the base of the fireplace.
Wall Thimble (required when
passing through a wall)
Gas line (3/8" M.P.T. or 1/2" F.P.T.)
should be routed 4-1/2" (114 mm)
behind the framing opening and 3-1/4"
(83 mm) above the base of the
fireplace on the right side (see "Gas
Line Connection" for details).
4 0 3 0 6 2 4
7