Installing the panel interface module
Terminals
RED & GRN (on J2)
Reader LED input
BPR & GND (on J2)
Sounder input
12V & GND (on J1)
Power input
The two NC terminals
Note:
on J2 are not used.
0
1 RE GRN BPR GN
Connect to access control panel/reader interface.
Figure 22d Connecting to the access control panel/
reader interface
Installation Instructions for 83KM/93KM–85KM/95KM IDH Max Cylindrical Locks
Installation Instructions for 83KM/93KM–85KM/95KM IDH Max Cylindrical Locks
Description
Input for the red and green LED control signal(s) from the access control
panel/reader interface. This input is configured using DIP switch 1 for either
one-wire LED operation or two-wire LED operation.
Two-wire LED operation: Connect the access control panel's/reader
interface's red LED output to the RED terminal and the access control panel's/
reader interface's green LED output to the GRN terminal. The reader's red LED
turns on when the access control panel/reader interface provides 0 volts DC to
the input for the red LED. The reader's green LED turns on when the access
control panel/reader interface provides 0 volts DC for the green LED.
One-wire LED operation: Connect the access control panel's/reader
interface's LED output to the RED terminal. The reader's LEDs are controlled as
shown below.
Input signal
LED response
0 volts DC
Green LED ON
5 volts DC
Red LED ON
Not driven
Both LEDs OFF
The signals provided to the Reader LED input and the Sounder input
Note:
must be greater than 3.5 volts DC to be interpreted as a 5 volts DC signal.
Signals with voltage less than 0.8 volts DC are interpreted as 0 volts DC
(connection to ground (GND).
Input for the sounder control signal from the access control panel/reader
interface. By default, the lock's sounder turns on when the access control
panel/reader interface closes the contact for the sounder, connecting the
panel interface circuit board's BPR terminal to ground (GND).
Input for 12 volts DC at 0.1 amp power supply.
Caution:
To prevent damage and injury, connect the power supply after
all other connections have been made.
2
NC
NC CP
BEST ACCESS SYSTEMS
a Product Group of Stanley Security Solutions, Inc
Connect to
12 VDC at
0.1 A supply.
Figure 22e Connecting to the power supply
Related DIP switches
DIP switch 1 configures
this input for one-wire
or two-wire operation.
DIP switch 7 provides
the ability to invert the
interpretation of the
sounder input signal.
None
1
21