Daikin E-Series Service Manual page 326

Hide thumbs Also See for E-Series:
Table of Contents

Advertisement

SiENBE18-621
Troubleshooting
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Turn power supply off, and
turn power supply on again.
Return to normal?
NO
Electronic
expansion valve is
connected to X21A and
X22A of outdoor unit
PC board
(A1P).
YES
Normal
when coil
check (*1) of the moving
part of the electronic
expansion valve is
checked.
YES
The connecting
cable is short-circuited or
disconnected.
NO
*Make measurement of resistance
between the connector pins, and
then make sure the resistance
falls in the range of 40 to 50W.
(Orange) 1
(Red) 2
(Yellow) 3
(Black) 4
5
(Gray) 6
YES
NO
NO
YES
Measuring points
1 - 6
2 - 6
3 - 6
4 - 6
Troubleshooting for Outdoor Unit
External factor other than
malfunction (for example, noise
etc.).
After connecting, turn the power
off and then back on again.
Replace the moving part of the
electronic expansion valve.
Replace the connecting cable.
Replace outdoor unit PC board
(A1P).
(V3067)
(V3067)
315