Field Setting - Daikin E-Series Service Manual

Hide thumbs Also See for E-Series:
Table of Contents

Advertisement

SiENBE18-621
4.2

Field Setting

4.2.1 Wired Remote Control
Note:
(Field setting must be made from the remote control in accordance with the installation
conditions.)
" Setting can be made by changing the "Mode number", "FIRST CODE NO.", and "SECOND
" Refer to the following procedures for Field setting.
Procedure
When in the normal mode, press the "
SET MODE is entered.
Select the desired MODE NO. with the "
During group control, when setting by each indoor unit (mode No. 20, 21 and 23 have been
selected), push the "
is unnecessary when getting by group.)
Push the "
Push the "
Push the "
Push the "
(Example) If during group setting and the time to clean air filter is set to FILTER CONTAMINATION -
HEAVY, SET MODE NO. to "10", FIRST CODE NO. to "0," and SECOND CODE NO. to "02".
UNIT NO.
SECOND
CODE NO.
FIRST
CODE NO.
Test Operation
CODE NO.".
" button for a minimum of four seconds, and the FIELD
" button and select the INDOOR UNIT NO to be set. (This operation
" upper button and select FIRST CODE NO.
" lower button and select the SECOND CODE NO.
" button once and the present settings are SET.
" button for about one second to return to the NORMAL MODE.
" button.
MODE NO.
FIELD
MODE
Field Setting for SkyAir Indoor Unit
SET
137