Daikin E-Series Service Manual page 283

Hide thumbs Also See for E-Series:
Table of Contents

Advertisement

Troubleshooting for RA Indoor Unit
Troubleshooting
Check No.06
Refer to P.279
272
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check the air passage.
Is there any short-circuit?
NO
Check the intake air filter.
Is it very dirty?
NO
Check the dust accumulation on
the indoor unit heat exchanger.
Is it very dirty?
NO
Check No. 06
Indoor unit heat exchanger
thermistor check
Does it conform to the
thermistor characteristic
chart?
NO
YES
YES
YES
YES
SiENBE18-621
Provide sufficient air passage.
Clean the air filter.
Clean the heat exchanger.
Replace the indoor unit PCB.
Replace the thermistor
(replace the indoor unit PCB).
(R4695)
Troubleshooting