SiENBE18-621
Fault diagnosis
Fault diagnosis by remote control
In the ARC433A series, the temperature display sections on the main unit indicate corresponding codes.
1. When the TIMER CANCEL button is held down for 5 seconds, a "00" indication flashes on the temperature
display section.
2. Press the TIMER CANCEL button repeatedly until a continuous beep is produced.
The code indication changes as shown below, and notifies with a long beep.
SYSTEM
INDOOR UNIT
OUTDOOR UNIT
NOTE
1. A short beep and two consecutive beeps indicate non-corresponding codes.
2. To cancel the code display, hold the TIMER CANCEL button down for 5 seconds. The code display also cancel
itself if the button is not pressed for 1 minute.
System Configuration
O N
C
HOME LEAVE
ON/OFF
TEMP
POWERFUL
MODE
FAN
SWING
SILENT
SENSOR
ON
CANCEL
OFF
TIMER
CODE
MEANING
00
NORMAL
U0
REFRIGERANT SHOTAGE
U2
DROP VOLTAGE OR MAIN CIRCUIT OVERVOLTAGE
U4
FAILURE OF TRANSMISSION (BETWEEN INDOOR UNIT AND
OUTDOOR UNIT)
A1
INDOOR PCB DEFECTIVENESS
A5
HIGH PRESSURE CONTROL OR FREEZE-UP PROTECTOR
A6
FAN MOTOR FAULT
C4
FAULTY HEAT EXCHANGER TEMPERATURE SENSOR
C9
FAULTY SUCTION AIR TEMPERATURE SENSOR
EA
COOLING-HEATING SWITCHING ERROR
E5
OL STARTED
E6
FAULTY COMPRESSOR START UP
E7
DC FAN MOTOR FAULT
E8
OPERATION HALT DUE TO DETECTION OF INPUT OVER CURRENT
F3
HIGH TEMPERATURE DISCHARGE PIPE CONTROL
F6
HIGH PRESSURE CONTROL (IN COOLING)
H6
OPERATION HALT DUE TO FAULTY POSITION DETECTION SENSOR
H8
CT ABNORMALITY
H9
FAULTY SUCTION AIR TEMPERATURE SENSOR
J3
FAULTY DISCHARGE PIPE TEMPERATURE SENSOR
J6
FAULTY HEAT EXCHANGER TEMPERATURE SENSOR
L4
HIGH TEMPERATURE AT INVERTER CIRCUIT HEATSINK
L5
OUTPUT OVERCURRENT
P4
FAULTY INVERTER CIRCUIT HEATSINK TEMPERATURE SENSOR
TIMER CANCEL button
It cancels the timer setting.
Instruction
225