9. Floor-Standing Type (F Type)

9-3. Other component specifications

MODEL NO.
Indoor Unit
Power Transformer
Rated
Primary
Secondary
Coil resistance
Thermal cut off temperature
Thermistor (Coil sensor)
Coil resistance
Thermistor (Room or coil sensor)
Coil resistance
Solenoid control valve or coil
Solenoid control valve
Solenoid coil
ECO MULTI SYSTEM Unit Specifications
V, Hz
WHT –WHT : 110
RED – RED : 2.3
˚C
PBC-41E-S25 , PBC-41E-S35
-10 ˚C : 23.7 ± 5 %
KΩ
-5 ˚C : 18.8 ± 5 %
0 ˚C : 15.0 ± 5 %
5 ˚C : 12.1 ± 5 %
10 ˚C : 9.7 ± 5 %
0 ˚C : 16.5 ± 5 %
KΩ
5 ˚C : 12.8 ± 5 %
10 ˚C : 10.0 ± 5 %
20 ˚C : 6.3 ± 5 %
30 ˚C : 4.0 ± 5 %
IKV-24D12 (SPW-F93 ~ 253GH56)
DKV-MOZS550E0 (SPW-F93 ~ 253GH56)
I - 115
SPW-F93 ~ 253GH56
ATR-II215TB
AC 230 V, 50 Hz
10.2 V 1.4 A
14 V 0.5 A
,
BRN – BRN : 0.5
145
20 ˚C : 6.5 ± 5 %
,
30 ˚C : 4.4 ± 5 %
,
40 ˚C : 3.1 ± 5 %
,
45 ˚C : 2.6 ± 5 %
,
KTEC-35-S6
40 ˚C : 2.7 ± 5 %
,
45 ˚C : 2.2 ± 5 %
,
50 ˚C : 1.8 ± 5 %
,
55 ˚C : 1.5 ± 5 %
,
1
SM830052