Sanyo SPW-C483GYH8 Service Manual page 130

Eco multi system
Table of Contents

Advertisement

10. Concealed Floor-Standing Type (FM Type)
Indoor unit (B)
MODEL No.
Source
Controller P.C.B. Ass'y
1
Fan (Number...diameter)
Fan motor
Model...Nominal output
Source
No. of pole...r.p.m. (230 V, High)
Coil resistance
(Ambient temperature 20°C)
Safety device
Operating temperature
Electronic refrigerating control valve
Solenoid control model
Coil resistance (at 20°C)
Solenoid control valve model
Heat exchanger
Coil
Rows...fin pitch
Face area
mm
W
rpm.
Open °C
Close °C
VAC, µF
Run capacitor
mm
m
ECO MULTI SYSTEM Unit Specifications
SPW-FM123GH56
220 - 230 - 240 V / 1 phase / 50Hz
CR-X253GH (Microprocessor)
Centrifugal (1 ... ø 153)
KFT4Q-21B3P ... 30 W
220 - 230 - 240 V / 1 phase / 50 Hz
BRN – WHT : 217.7
WHT – VLT
: 37.33
VLT – ORG : 22.48
440 V, 2.0 µF
DKV-MOZS550E0
ORG – GRY : 46 ,
RED – GRY : 46 ,
Aluminum plate fin / Copper tube
2
I - 124
4 ... 1,102
ORG – YEL
: 37.88
YEL – PNK
: 21.82
°C
148
+ 0
– 5
YEL – GRY : 46
BLK – GRY : 46
IKV-24D12
3 ... 2.0
0.102
SM830052

Hide quick links:

Advertisement

Table of Contents
loading