Major Component Specifications - Sanyo SPW-C483GYH8 Service Manual

Eco multi system
Table of Contents

Advertisement

6. Ceiling Mounted Type

6-2. Major component specifications

Indoor unit (A)
MODEL No.
Source
Controller P.C.B. Ass'y
1
Fan (Number...diameter)
Fan motor
Model...Nominal output
Source
No. of pole...r.p.m. (230 V, High)
Coil resistance
(Ambient temperature 20 °C)
Safety device
Operating temperature
Run capacitor
Electronic refrigerating control valve
Solenoid control model
Coil resistance (at 20 °C)
Solenoid control valve model
Heat exchanger
Coil
Rows...fin pitch
Face area
Auto louver motor
Auto louver motor...Rated
Coil resistance (at 25 °C)
Dew proof heater
ECO MULTI SYSTEM Unit Specifications
mm
W
rpm.
BRN – WHT : 159.4
WHT – VLT
VLT – ORG :
Open °C
Close °C
VAC, µF
ORG – GRY : 46 ,
RED – GRY : 46 ,
mm
2
m
V, Hz, W, rpm.
220 – 240 VAC, 50 Hz, 3 W, 3.3 rpm., 8 P
V, W
I - 70
SPW-T183GH56
220 - 230 - 240 V / 1 phase / 50 Hz
CR-X253GH (Microprocessor)
Centrifugal (3 ... ø 130)
SR4Q-31A5P ... 30 W
220 - 230 - 240 V / 1 phase / 50 Hz
4 ... 1,111
ORG – YEL
:
26.6
YEL – PNK
23.9
130 ±
5 °C
Differential 15 deg. (min.)
440 V, 1.8 µF
DKV - MOZS550E0
YEL – GRY : 46
BLK – GRY : 46
IKV-24D12
Aluminum plate fin / Copper tube
2 ... 1.7
0.145
MC8 D
14,900 Ω ± 8 %
240 V, 12 W
:
75.8
:
26.6
SM830052

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents