Sanyo SPW-C483GYH8 Service Manual page 17

Eco multi system
Table of Contents

Advertisement

1. Outdoor Unit
Outdoor Unit (C)
MODEL No.
Source
Controller P.C.B. Ass'y
Control circuit fuse
Compressor
Model ... Code No.
Nominal output
Compressor oil (SUNISO 4GSD-T) cc
Coil resistance
(Ambient temperature 25°C)
Safety devices
Thermal protector ON / OFF
Microprocessor safety devices
Crank case heater
Fusible plug (Operating temp.)
High pressure switch
Set pressure
ON / OFF
Fan (Number ... diameter(mm))
Fan motor
Model ... Nominal output
No. of pole ... r.p.m. (230 V, High)
Coil resistance
(Ambient temperature 20 °C)
Safety device
Thermal protector ON / OFF
Run capacitor
Heat exchanger
Coil
Rows ... fin pitch
Face area
PC (Power Control)
C-5R433H8U ... 80843688
kW
2,000
V - U: 2.76 , U - W: 2.59
W - V: 2.71
°C
120 ± 5 / 98 ± 11
Compressor current detection circuit
Compressor discharge gas temperature control
Defective and negative phase detection circuit
Voltage drop detection circuit
V, W
240 , 32
°C
kg/cm
2
W
°C
VAC , µF
mm
2
m
I - 11
ECO MULTI SYSTEM Unit Specifications
SPW – C903GYH8 / SPW – C903GY8
380 - 400 - 415 V / 3 phase / 50Hz
CR - C703GYH / CR - C703GY
250 V , 3.15 A
Rotary (Hermetic)
C-5R433H8A ... 80843588
4.3
V - U: 2.76 , U - W: 2.59
W - V: 2.71
73 ± 2
ACB - 1TB04W (TUV Approved)
24 ± 2.0 / 30
+ 0
– 1. 5
Propeller (1 ... ø 750)
KFS8T - 201C3P ... 200W
8 ... 567 r.p.m.
BRN - WHT :
WHT - VLT :
VLT - YEL :
YEL - PNK :
125 – 15 / 130 ± 5
440 V , 15.0 µF
Aluminum plate fin / Copper tube
2 ... 1.7
2.40
AC (Standard)
4.3
2,000
120 ± 5 / 98 ± 11
240 , 32
9.42
4.59
5.85
3.33
SM830052
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents