1. Troubleshooting
(B) Use the test run procedure
The purpose of the test run function is to let you control the operation of the unit directly without turning the
unit on or off by thermostat. As indicated in the following procedure, be sure to stop test run operation when
you finish the procedure, or the air conditioner may be damaged because it won't turn on and off normally.
To protect the air conditioner from overloading, the outdoor unit will not start running for 3 minutes after power
is applied or the unit is turned OFF.
a
Press the TEST / CHK button at the bottom
right on the remote controller.
b
Press the ON / OFF operation button to start
the test run.
c
Press the MODE button to select either
COOLING or HEATING mode.
d
When the test run starts, "TEST" shows on
the remote controller's display.
e
During the test run, the air conditioner runs
continuously and the thermostat does not
control the system.
f
After the test run, be sure to press the
TEST / CHK button once again to finish this
3
mode and be sure "TEST" is not shown on
the display.
CAUTION
The TEST RUN button is used only for servicing the air conditioner. Do not press this button in normal operation, or
the system may be damaged.
AIR FLOW
UNIT
FLAP
TIMER SET
A
SET
CL
Alarm message
ON / OFF operation
button
III - 24
Service Procedures
MODE
°C
SET TEMP.
FAN SPEED
TEST
ON
OFF
TEST / CHK
TEST RUN / CHECK button